OverviewThe Ultra K34 sprinkler delivers the industry's highest ceiling-only fire protection for cold storage. By eliminating in-rack sprinklers it increases usable storage volume and reduces the risk of accidental activations. The Ultra K34 is FM Approved and intended for dry or preaction Quell / VanQuish performance-based systems; it has passed full-scale FM Global fire tests for ceiling-only storage of Class III commodities.
Benefits- Maximize storage volume: Industry-leading ceiling-only protection for cold storage enables denser storage layouts.
- Lower costs and greater flexibility: Removing in-rack sprinklers reduces damage risk and allows reconfiguration of storage arrays without fire protection redesign.
- Proven performance: Supported by 15 full-scale fire tests across multiple commodity types, storage arrangements and ceiling/storage heights.
Technical specificationApprovals | FM Approved
Hazard classification | Storage / Class III
Orientation | Upright
K-Factor | 33.6
Temperature rating | 286°F (141°C)
Response | Standard
Thread | 1 ¼-inch
SIN Number | TY9101
Installation note | To be installed only by a licensed Quell / VanQuish contractor in accordance with the applicable technical data sheet
Key specifications- Approvals: FM Approved
- Hazard: Storage / Class III
- Orientation: Upright
- K‑Factor: 33.6
- Temperature rating: 286°F (141°C)
- Response: Standard
- Thread size: 1 ¼-inch
- SIN Number: TY9101
- Installation: Licensed Quell / VanQuish contractor per technical data sheet