Liquid dilation thermostat 9030-41
adjustableIP40manual reset

liquid dilation thermostat
liquid dilation thermostat
Add to favorites
Compare this product
 

Characteristics

Heating technology
liquid dilation
Type
adjustable
Protection level
IP40
Other characteristics
manual reset
Temperature

Max.: 100 °C (212 °F)

Min.: 10 °C (50 °F)

Description

Box containing a adjustable thermostat between 10°C to 90°C and a temperature cut-out, pre-set to 100°C, with manual reset. Circuit is open if the sensor is broken. Simple to install and use, these box-mounted liquid-expansion thermostats are fixed to the tank (or pipe) and heated via the supplied copper thermowell. IP40 box. Copper probe, length 95mm. Thermostat : single-pole double-throw contacts, breaking capacity 15A at 250V, 10Aat400V. Cut-out: normally close contact Differential 6°K, Max. working pressure: 10 bar.