The UHV-505 is a portable, all-in-one on-site cable diagnostic system that performs non-destructive testing using Damped AC Voltage (DAC) up to 30 kV. It combines partial discharge (PD) detection and dielectric loss measurement to evaluate insulation defects and ageing, and supports cloud upload for remote analysis and predictive maintenance.
Product features- Advanced semiconductor-based high-voltage generation and control
- Laser-triggered high-voltage switch for precise timing control
- High-performance digital signal processing with advanced filtering
- Intelligent wireless and wired network control
- Cloud-based data management for remote review, multi-terminal WEB access and reporting
Main functions of system software- Record test time and date
- Manage registered users and test personnel information
- Store test cable basic data: station name, cable model, length, joints, operation history
- All-Chinese operation interface (localized UI as supplied)
- One-key compression, automatic calibration and one-key analysis functions
- Intuitive voltage-amplitude setting with automatic boost and oscillatory wave generation control
- Multi-terminal web browsing of cloud test data and automatic synchronization of basic parameters (network required)
- Automatic display of oscillation amplitude, oscillation frequency and sampling window
- Automatic display of dielectric loss value and maximum PD magnitude
- Store oscillation waveform and local discharge waveform; on-site amplification of local discharge waveform for initial source positioning
- Automatic or manual analysis of detection data with automatic generation of discharge location maps and statistical reports (e.g., Q-φ chart, N-φ chart)
Technical specifications- Power supply: 220VAC ±10%, 50Hz
- Maximum output voltage (peak): 30 kV
- Oscillation frequency range: 20 Hz – 500 Hz
- Test cable length range: 200 m – 20 km
- High-voltage charging current: 8 mA
- High-voltage switch trigger: Laser triggers high-voltage switch; conduction time: 1 μs; switching resistance: < 1 Ω; optical fiber communication for control
- Local discharge measuring range: 1 pC – 100 nC
- Local discharge detection level and bandwidth: compliant with IEC 60270
- Emission/localization bandwidth: 150 kHz – 45 MHz (automatic adjustment)
- Local discharge positioning accuracy: 1% of cable length (minimum resolution 2 m)
- Dielectric loss measurement range: 0.1% – 10%
- Real-time waveform sampling rate: 100 MHz
- Local sampling storage depth: 32 MB (records up to 300 ms)
- Control modes: wireless control and wired control
- Local discharge calibration: automatic / manual
- Damped oscillatory wave implementation: automatic voltage boost and automatic generation of damped oscillatory wave