DescriptionThe DLC compact surge protective device DLC-06D2 is a non-pluggable monobloc unit designed to protect 1-pair telecom, data and industrial signalling lines from lightning and transient overvoltages. It is mounted on a symmetrical 35 mm DIN rail inside customer distribution or control panels. Available in D2, D3 and D3G variants to address floating lines, full-mode protection and signalling-ground protection respectively.
Key features- Supports high-speed data transmission (cut-off >110 MHz)
- Common-mode and differential-mode protection
- 1-pair protection with shield conductor monitoring
- Compact DIN-rail form factor for high-density installations
- Failsafe short-circuit disconnect and transmission-interrupt end-of-life indicator
- IEC 61643-21 / EN 61643-21 compliance
Applications- 4–20 mA loops and 24 V control / data links
- Telecommunication and data communication lines
- Signalling, SCADA and industrial automation interfaces
Technical specifications- Reference / Model: DLC-06D2
- Part number: 641181
- Network type: Data communication / Telecom
- Nominal line voltage (Un): 6 V
- Max. DC operating voltage (Uc): 8 Vdc
- Cut-off frequency (-3 dB, 100 Ω): > 110 MHz
- Cut-off frequency (-1 dB, 100 Ω): > 60 MHz
- Insertion loss: < 1 dB
- Max. load current @25°C (IL): 750 mA
- Max. discharge current Imax (8/20 µs per pole): 20 kA
- Nominal discharge current Line/Earth (In L/PE, C2): 10 kA
- Protection level Up (C3 10/1000 µs) Line/Line: 30 V
- Protection level Up (C3 10/1000 µs) Line/Earth: 650 V
- Impulse current (2×10/350 µs, D1) Iimp: 2.0 kA
- Line resistance: 1.2 Ω (±10%)
- Technology: GDT + TVS diode
- SPD configuration: 1-pair + shielded
- Connection: Spring terminal, max cross section 2.5 mm² / AWG 13
- Mounting: Symmetrical DIN rail 35 mm (EN 60715)
- Housing: Thermoplastic UL94 V-0, IP20
- Operating temperature: -40 to +85 °C
- Weight: 0.029 kg
- Standards: IEC 61643-21 / EN 61643-21
Compliance & safety- Failsafe short-circuit disconnect mode
- Transmission-interrupt end-of-life indicator (default mode 2)
- Test and location categories: D1, C2, C3