Overview- Universal combined arrester with a base part and a plug-in protection module
- Device concept specifically developed for use in DC circuits and DC charging equipment
- Integrated DCD DC switching device reduces risk of fire from DC switching arcs
- Can be used without additional backup fuse in defined application scenarios
- Operating / fault state indicated mechanically by green / red flag in the inspection window
- Tool-free replacement of protection modules via locking system with module release button
Variant — DEHNguard M DC ACI 1250 FM (Part No. 972150)Modular surge arrester for DC applications; with floating remote signalling contact.
- Surge protective device Type 2, DG M DC ACI 1250 FM
- Modular, pluggable surge arrester
- For DC applications, width of 6 DIN modules
- Mechanical operating / fault state indication
- Type 2 arrester similar to EN / IEC 61643-41
- Consisting of switch / spark gap combination
- Specially for use in DC charging equipment up to 1,250 V
- Max. continuous operating voltage (+ --> -): 1250 V DC
- Nominal discharge current (8/20 µs): 10 kA
- Max. nominal impulse discharge current (8/20 µs): 20 kA
- Max. short-circuit withstand capability (ISCCR): 5 kA
- Floating remote signalling contact as changeover contact
Technical details (Part No. 972150)- SPD classification similar to EN 61643-41 / IEC 61643-41 — Type 2
- Nominal discharge current (8/20 µs) (In) — 10 kA
- Max. nominal impulse discharge current (8/20 µs) (Imax) — 20 kA
- Max. short-circuit withstand capability (ISCCR) — 5 kA
- Type of remote signalling contact — changeover contact
- Extended technical data — see variant documentation
Additional product information / Tender specification (Part No. 972150)- Surge protective device Type 2, DG M DC ACI 1250 FM
- Modular, pluggable surge arrester
- For DC applications, width of 6 DIN modules
- Mechanical operating / fault state indication
- Type 2 arrester similar to EN / IEC 61643-41
- Consisting of switch / spark gap combination
- Specially for use in DC charging equipment up to 1,250 V
- Max. continuous operating voltage (+ --> -): 1250 V DC
- Nominal discharge current (8/20 µs): 10 kA
- Floating remote signalling contact as changeover contact
- Vibration and shock-tested according to EN 60068
- Fulfils IEC 61851-23
Technical specifications- Product family: DEHNguard ME/SE DC ... (FM)
- Design: modular combined arrester (base part + plug-in protection module)
- Intended use: DC circuits, including DC charging equipment (variants up to 1250 V DC)
- Remote signalling: floating changeover contact (variant dependent)
- DCD DC switching device: prevents fire damage from DC switching arcs (variant dependent)
- SPD classification: Type 1+2 or Type 2 depending on variant and configuration
- Nominal discharge current (8/20 µs): typical values 10 kA or 12.5 kA (variant dependent)
- Max. nominal impulse discharge current (8/20 µs): up to 20 kA
- Lightning impulse current (10/350 µs): e.g. 5 kA on combined (ME) variants
- Voltage protection levels (Up): variant dependent (examples: <0.5 kV, <1.25 kV, <2.0 kV, <3.0 kV)
- Short-circuit withstand capability (SCCR): variant dependent (examples: 5 kA, 300 A, 25 kA etc. depending on model and backup fuse conditions)
- Max. continuous operating voltage (UC): variant examples: 60 V DC, 242 V DC, 550 V DC, 900 V DC, 1000 V DC, 1250 V DC
- Module widths: variants from 1.5 modules up to 6 DIN modules (model dependent)
- Fault indication: mechanical green / red indicator flag in inspection window
- Module replacement: tool-free module locking system with release button