Short descriptionModular surge arrester for d.c. applications with floating remote signalling contact.
Key features- Universal combined arrester/ surge arrester consisting of a base part and a plug-in protection module
- Device concept specifically developed for use in d.c. circuits
- Powerful d.c. switching device (DCD) prevents fire damage caused by d.c. switching arcs
- Use without additional backup fuse in defined applications
- Operating state / fault indication by green / red indicator flag in the inspection window
- Easy replacement of protection modules without tools due to module locking system with module release button
- Floating remote signalling contact (changeover contact)
- Modular, pluggable design; width of 6 DIN modules
Product details / Tender specificationsSurge protective device Type 2, DG M DC ACI 1250 FM
Modular, pluggable surge arrester for DC applications, width of 6 DIN modules
Mechanical operating / fault state indication
Type 2 arrester similar to EN / IEC 61643-41
Consisting of switch/spark gap combination
Specifically for use in DC charging equipment up to 1,250 V DC
Max. continuous operating voltage (+ --> -): 1250 V DC
Nominal discharge current (8/20 µs): 10 kA
Floating remote signalling contact as changeover contact
Vibration and shock-tested according to EN 60068
Fulfils IEC 61851-23
Technical details (table)SPD classification similar to EN IEC 61643-41: Type 2
Nominal discharge current (8/20 µs) (In): 10 kA
Max. nominal impulse discharge current (8/20 µs) (Imax): 20 kA
Max. short circuit withstand capability (ISCCR): 5 kA
Type of remote signalling contact: changeover contact
Application / Functional descriptionUniversal combined arrester with base part and plug-in protection module for protection of low-voltage consumer installations against surges.
Device concept and DCD switching device designed for safe operation in d.c. circuits and for use in DC charging equipment up to 1,250 V DC.
Mechanical operating / fault indication and easy tool-free replacement of protection modules.
Technical specifications- Brand: DEHN
- Type / Model: DEHNguard M DC ACI 1250 FM
- Part No.: 972150
- GTIN (EAN): 4013364530850
- Max. continuous operating voltage: 1250 V DC
- Nominal discharge current (8/20 µs): 10 kA
- Max. nominal impulse discharge current (8/20 µs): 20 kA
- Max. short circuit withstand capability (ISCCR): 5 kA
- Remote signalling: floating changeover contact
- Width: 6 DIN modules (modular, pluggable)
- Standards / Tests: EN / IEC 61643-41 (Type 2), EN 60068 (vibration/shock), IEC 61851-23
- Packaging unit: 1 ST