OverviewEnergy Analyzer and Web Data Manager with accuracy class 0.5S and harmonic analysis up to the 51st order. Designed for use with external ECT current transformers (CTs not included; example codes PFAE000-01, PFAE000-02, PFAE000-03). Provides a network bridge between the RJ45 port and RS485 port for Modbus communication with other Electrex instruments in the subnet and related data storage. Features a perennial battery-powered clock, non-volatile memory, remote firmware update, LCD graphic display and two calibration LEDs. ExpBus enables external I/O and environmental sensor connections. NFC connectivity and DIN rail mounting (6 modules). Power supply 85 ÷ 265 Vac. Compliant with EN 50470-1 and EN 50470-3.
Included upgrades- PFSU940-01 Log 8
- PFSU940-05 Web
Additional notesDevices from the Femto ECT RJ45, Femto ECT net, Femto 25A D RJ45 or Femto 25A D families can be ordered in alternative hardware configurations. Refer to the product sheet code creation table to build specific part codes. Femto ECT units require external ECT CTs (not included); see the accessories section.
Caractéristiques / spécifications techniques- Accuracy class: 0.5S
- Harmonics: single harmonics up to the 51st order
- Compatible CTs: external ECT CTs required (not included); example codes: PFAE000-01, PFAE000-02, PFAE000-03
- Network: bridge between RJ45 port and RS485 port for Modbus communication
- Data storage & clock: perennial battery-powered clock and non-volatile memory
- Firmware: remote firmware update supported
- Display: LCD graphic display
- Indicators: 2 calibration LEDs
- Expansion: ExpBus for external inputs/outputs and environmental sensors
- Connectivity: NFC
- Mounting: DIN rail, 6 modules
- Power supply: 85 ÷ 265 Vac
- Standards compliance: EN 50470-1, EN 50470-3
- Package contents: device and listed upgrades; external ECT CTs not included