UV flame detector R13192

UV flame detector
UV flame detector
Add to favorites
Compare this product
 

Characteristics

Technology
UV

Description

The R13192 delivers enhanced sensitivity through a new design of the photosensitive area. Features Detects fire from long distances (high sensitivity) Detects only UV light without using any optical filters Applications Fire detection in a building with large space Arson surveillance Discharge detection Specifications Spectral Response (Short) : 185 nm Spectral Response (Long) : 260 nm Electrode Material : Ni Weight : 5.2 g [Maximum Rating] Supply Voltage (DC) : 420 V [Maximum Rating] Average Discharge Current : 3 mA [Maximum Rating] Peak Current : 50 mA [Maximum Rating] Operation Ambient Temperature : -40 to +125 ℃ Discharge Starting Voltage (DC) : 260 V Discharge Sustaining Voltage (DC) : 185 V Sensitivitiy Typ. : 15000 min-1 Background Max. : 5 min-1 Average Life : 25000 h [Recommended Operating Parameters] Supply Voltage (DC) : 325±25 V [Recommended Operating Parameters] Average Discharge Current : 0.3 mA [Recommended Operating Parameters] Quenching Time Min. : 2 ms Suitable Socket (Sold Separately) : E678-9C

Exhibitions

Meet this supplier at the following exhibition(s):

ACHEMA 2024
ACHEMA 2024

10-14 Jun 2024 Frankfurt am Main (Germany) Hall 11.1 - Stand F62

  • More information

    Other HAMAMATSU products

    UV & flame sensors

    *Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.