1. Hydraulics - Pneumatics
  2. Valve
  3. Ball valve
  4. Honeywell Environmental & Combustion Controls EMEA
video corpo

Ball valve V5004TY series
manualfor controltemperature control

Ball valve - V5004TY series  - Honeywell Environmental & Combustion Controls EMEA - manual / for control / temperature control
Ball valve - V5004TY series  - Honeywell Environmental & Combustion Controls EMEA - manual / for control / temperature control
Ball valve - V5004TY series  - Honeywell Environmental & Combustion Controls EMEA - manual / for control / temperature control - image - 2
Ball valve - V5004TY series  - Honeywell Environmental & Combustion Controls EMEA - manual / for control / temperature control - image - 3
Ball valve - V5004TY series  - Honeywell Environmental & Combustion Controls EMEA - manual / for control / temperature control - image - 4
Ball valve - V5004TY series  - Honeywell Environmental & Combustion Controls EMEA - manual / for control / temperature control - image - 5
Add to favorites
Compare this product

Characteristics

Type
ball
Operation
manual
Function
for control, temperature control, flow control
Media
for air
Body
threaded
Applications
heating, for pipes, coil
Other characteristics
standard, automatic, modulating, pressure-independent
DN

Min.: 15 mm
(0.591 in)

Max.: 50 mm
(1.969 in)

Pressure

16 bar
(232.1 psi)

Temperature

Min.: -10 °C
(14 °F)

Max.: 120 °C
(248 °F)

Flow rate

Min.: 45 l/h
(11.89 us gal/h)

Max.: 18,000 l/h
(4,755.1 us gal/h)

Description

V5004TY Series pressure independent control valves combine a differential pressure regulating mechanism with a full stroke control valve to achieve optimized flow control across a wide spectrum of varying system pressures and flow rates. The V5004TY pressure independent control valve normalizes the differential pressure across the control valve portion, enabling it to maintain a constant flow rate without changing the actuator position. This provides stable flow and stable system conditions, to optimize equipment use, energy use, and performance. It is suitable for use in variable and constant flow systems, as flow limiter in constant flow systems (without an actuator), or with an actuator as a pressure independent control valve. Typical use is control of fan coil units, air handling units, chilled ceilings and two-pipe heating systems. The mechanism reduces actuator movements resulting from pressure fluctuations, which will extend actuator life. No complex calculation is needed for selection, simply pick a valve with a suitable maximum flow rate range to suit the application and connection sizes used. No hydronic balancing is needed for commissioning. Sizes available from DN15 to DN50, types A and B are PN25 and type E is PN16.