Water chiller Ultracool UC 50
glycol waterfor refrigerationindustrial

Water chiller - Ultracool UC 50 - LAUDA DR. R. WOBSER GMBH & CO. KG - glycol water / for refrigeration / industrial
Water chiller - Ultracool UC 50 - LAUDA DR. R. WOBSER GMBH & CO. KG - glycol water / for refrigeration / industrial
Add to favorites
Compare this product

Characteristics

Material
water, glycol water
Applications
industrial, for refrigeration, for industrial operation
Other characteristics
high-pressure, high-performance, IP54, water cooler, with water pump
Maximum temperature

Min.: -10 °C
(14 °F)

Max.: 35 °C
(95 °F)

Flow rate

Min.: 9 m³/h
(317.832 ft³/h)

15 m³/h, 150 m³/h, 292 m³/h
(39.626 ft³/h, 66.043 ft³/h, 77.138 ft³/h)

Max.: 17.52 m³/h
(618.713 ft³/h)

Pressure

5 bar, 5.6 bar
(0.001 psi, 72.519 psi)

Description

Product description
LAUDA Ultracool UC 50 circulation chiller provides precise temperature control over an extended working range from -10 to 35 °C with a temperature stability of ±0.5 K. Protection class IP54 allows outdoor installation. Standard fan control enables operation at ambient temperatures down to -20 °C and reduces noise emission. The unit has a reduced footprint compared to previous models and features an integrated Ethernet interface. Numerous options (e.g. speed-controlled pumps, flow meters) allow customer-specific configuration. Part no.: L004664

Key features
  • Industrial circulation chiller for process cooling
  • Industrial block pump with high pressure and high flow
  • Compatible with non-flammable heat transfer fluids (water, water/glycol)
  • Operation and monitoring via integrated web server
  • Integrated water filter
  • Designed to meet EcoDesign directive 2009/125/EC requirements
  • Temperature control via PID controller
  • Integrated Ethernet interface
  • Uses natural refrigerants


Working range
  • Min. working temperature: -10 °C
  • Max. working temperature: 35 °C
  • Temperature stability: ±0.5 K
  • Ambient temperature range: -20 … 50 °C


Cooling capacity
Temperature | Cooling capacity 50 Hz | Cooling capacity 60 Hz
25 °C | 74.5 kW | 74.5 kW
20 °C | 67 kW | 67 kW
15 °C | 60 kW | 60 kW
10 °C | 51.2 kW | 51.2 kW
5 °C | 45.3 kW | 45.3 kW
0 °C | 37.9 kW | 37.9 kW
-5 °C | 31.9 kW | 31.9 kW
-10 °C | 26.7 kW | 26.7 kW


Technical data (according to DIN 12876)
  • Working temperature range: -10 … 35 °C
  • Ambient temperature range: -20 … 50 °C
  • Temperature stability: ±0.5 K
  • Max. filling volume: 125 L
  • Max. discharge pressure: 5.0 bar (50 Hz); 5.6 bar (60 Hz)
  • Max. pump flow (pressure): 250 L/min (50 Hz); 292 L/min (60 Hz)
  • Nominal pump flow rate: 150 L/min
  • Inlet/outlet connection thread (internal): Rp 1 1/2
  • Dimensions (W×D×H): 1040 x 1435 x 1890 mm
  • Weight: 410 kg
  • Noise level: 68.7 dB(A)
  • Power supply: 400 V; 3/PE; 50 Hz & 460 V; 3/PE; 60 Hz
  • Protection class: IP 54 (suitable for outdoor installation)
  • Interfaces: Integrated Ethernet; web server operation


Downloads (examples)
Data sheet Ultracool UC 50 (PDF), SEPR Certificate UC50 (PDF), Ultracool New Generation brochure (PDF), Ultracool New Generation supplement (PDF)

Accessories
  • Extension cable (accessory A001558)
  • Extension cable (accessory A001559)
  • Additional accessories available via LAUDA accessory finder

VIDEO

Catalogs

No catalogs are available for this product.

See all of LAUDA DR. R. WOBSER GMBH & CO. KG‘s catalogs
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.