Characteristics

Material
water, glycol water
Applications
industrial
Other characteristics
compact, high-pressure, outdoor, IP54
Maximum temperature

Min.: -10 °C
(14 °F)

Max.: 35 °C
(95 °F)

Flow rate

84.1 l/min, 166 l/min, 200 l/min
(22.217 us gal/min, 43.853 us gal/min, 52.834 us gal/min)

Pressure

4.7 bar, 6.8 bar
(68.168 psi, 98.626 psi)

Description

Product overview
LAUDA Ultracool circulation chillers provide precise temperature control across an extended operating range from -10 to 35 °C with temperature stability of ±0.5 K. IP54 protection allows outdoor installation; standard fan control enables operation at ambient temperatures down to -20 °C and reduces noise. The design reduces footprint compared to previous models. Standard Ethernet interface and numerous options (speed-controlled pumps, flow meters) permit customer-specific configurations.

Features
  • Industrial circulation chiller
  • Industrial monoblock pump with high pressure and high flow
  • Operates with non-flammable fluids (water, water/glycol)
  • Remote operation via web server
  • Integrated water filter
  • Meets Ecodesign directive 2009/125/EC energy efficiency requirements
  • PID temperature control
  • Integrated Ethernet interface
  • Uses natural refrigerants


Working range
  • Minimum operating temperature: -10 °C
  • Maximum operating temperature: 35 °C
  • Temperature stability: ±0.5 K
  • Ambient temperature range: -20 … 50 °C


Cooling capacity (examples)
Temperature | Cooling capacity 50 Hz | Cooling capacity 60 Hz
25 °C | 37.1 kW | 37.1 kW
20 °C | 33.2 kW | 33.2 kW
15 °C | 29.6 kW | 29.6 kW
10 °C | 25.9 kW | 25.9 kW
5 °C | 21.9 kW | 21.9 kW
0 °C | 18.8 kW | 18.8 kW
-5 °C | 16.1 kW | 16.1 kW
-10 °C | 13.8 kW | 13.8 kW

Technical specifications
  • Model: Ultracool UC 24
  • Maximum filling volume: 35 L
  • Maximum discharge pressure: 4.7 bar (50 Hz); 6.8 bar (60 Hz)
  • Maximum pump flow (pressure): 166 L/min (50 Hz); 200 L/min (60 Hz)
  • Nominal pump flow rate: 84.1 L/min
  • Connection thread (in/out): Rp 1
  • Dimensions (W×D×H): 720 × 910 × 1250 mm
  • Weight: 180 kg
  • Sound level: 64.7 dB(A)
  • Power supply: 400 V; 3/PE; 50 Hz & 460 V; 3/PE; 60 Hz
  • Protection class: IP 54