- Peltier gas cooler with 2 independent gas paths
- For 2 Jet-Stream heat exchangers with a gas flow rate of max. 2 x 150 Nl/h
- Can be used up to an ambient temperaure [+122 °F] as standard
- Adjustable gas outlet dew point with a stability of < ±0.1 °C [±0.18 °F] at constant conditions
- Control setpoint selectable between absolute and differential temperature value mode
- With a total cooling capacity of 2 x 90 kJ/h at +25 °C [+77 °F] ambient temperature
- Universally usable with broadband power supply
- Configurable, potential-free alarm output
- Integrated evaluation for liquid alarm sensors LA1 and LA1S
- Optionally: 2 Jet-Stream heat exchangers, automatic or manual condensate removal, 2 configurable mA outputs (no shielding necessary), measuring of the gas outlet temperature in the gas paths
The ECP 2000C gas cooler is used in gas analysis to lower the dew point of humid to avoid condensation in the analyser. An extremly stable gas dew point avoids water vapour crosssensitivity and volumetric errors.
Electric gas cooler type ECP2000C with display and capacitive control panel, for ambient temperatures , with Peltier element, electronically controlled between +2 and +15 °C (pre‑set to +5 °C), adjustable high/low‑temperature alarm with 2 potential‑free relay contacts, integrated LA evaluation, without heat exchanger, power: 115 to 230 V AC/50 to 60 Hz pluggable