GeneralThe YBTD series substation is designed for integration with wind power and photovoltaic generation. It provides a modular housing, configurable HV/LV compartments and transformer options to suit on-site requirements.
Service conditions- Altitude: ≤ 1000 m
- Ambient temperature: max +40°C, min -25°C
- Max daily average temperature: ≤ 35°C
- Max annual average temperature: ≤ 25°C
- Max daily temperature difference: ≤ 25°C
- Solar radiation: ≤ 1000 W/m²
- Wind speed: ≤ 34 m/s
- Icing thickness: ≤ 20 mm
- Pollution level: Class II
- Installation tilt: ≤ 3°
- Seismic: horizontal ground acceleration 0.2 g; vertical 0.1 g
- Installation site: free from fire, explosion risk, severe chemical corrosion or strong vibration
Structure features- Housing structure: Substation skeleton manufactured from channel and angle steel. Shell options: cold-rolled steel plate, stainless steel, composite color plate, aluminium-alloy plate or glass-fibre reinforced cement. Steel-plate partitions between compartments and integrated lighting. Double-layer cover for thermal control. Transformer room configurable as open (radiator outdoors) or closed (independent chamber with automatic exhaust). Low-temperature seals on doors and high-temperature surface coating for UV resistance.
- HV unit: High-voltage switchgear options (e.g. XGTD9, HXGN11, XGTD6, (H)XGTD10). Designs prioritise compact layout, safe interlocks and ease of installation and maintenance.
- Transformer unit: Use of S9-M / S11-M oil-immersed transformers or SCB dry-type transformers. Transformer room supports natural or forced ventilation. Flexible connections on LV terminals protect bushings and prevent oil leakage.
- LV unit: LV switchgear choices include GGD, GCS and GCK series. Metering, protection and automatic power‑factor compensation can be configured per project requirements.
- Distribution network automation unit: Terminal automation equipment optimised for harsh environments: wide temperature tolerance, dual-fibre ring communication, high immunity to interference, vibration, humidity and lightning, low power consumption. Provides automatic monitoring interfaces for wind and PV transformers.
Technical dataRated HV voltage: 40.5 kV
Rated frequency: 50 / 60 Hz
Rated HV current options: 630 A / 1250 A
1 min power-frequency withstand voltage (ground/phase): 95 / 118 kV
Lightning impulse withstand voltage (ground/phase): 185 / 215 kV
Rated short-time withstand current: 20 kA/2 s ; 25 kA/4 s
Rated peak withstand current: 50 kA ; 63 kA
Rated short-circuit current examples: 31.5 kA ; 63 kA
Rated short-circuit breaking current examples: 31.5 kA ; 25 kA
LV rated voltage: 690 / 270 V
Main circuit rated current: 1600 ~ 3300 A
Rated ultimate short-circuit breaking capacity: 50 kA
Rated short-circuit breaking capacity: 40 kA
Rated short-time withstand current (LV): 40 kA/1 s
Transformer rated capacity: 1000 ~ 5500 kVA
Impedance voltage: 6.5 %
Tap range: ±2×2.5 % ; ±5 %
Connection group: D, yn11 or Y, d11/d11
Enclosure protection: HV room IP33; LV room IP33; Transformer room IP23
Sound level: ≤ 55 dB
NoteParameters shown are for reference. Site-specific customization and engineering options are available on request.
Characteristics / technical specifications- Series: YBTD substation for wind and photovoltaic integration
- Rated HV voltage: 40.5 kV
- Rated frequency: 50 / 60 Hz
- HV rated current options: 630 A, 1250 A
- LV rated voltage: 690 / 270 V
- LV main circuit rated current range: 1600–3300 A
- Transformer capacity range: 1000–5500 kVA
- Transformer impedance: 6.5 %
- Tap range: ±2×2.5 % ; ±5 %
- Protection degrees: HV/LV IP33, Transformer IP23
- Noise level: ≤ 55 dB