Power distribution substation ZBW -12(24) HV/LV
compactprefabricated

Power distribution substation - ZBW -12(24) HV/LV - Ningbo Tianan (Group) CO.,Ltd. - compact / prefabricated
Power distribution substation - ZBW -12(24) HV/LV - Ningbo Tianan (Group) CO.,Ltd. - compact / prefabricated
Power distribution substation - ZBW -12(24) HV/LV - Ningbo Tianan (Group) CO.,Ltd. - compact / prefabricated - image - 2
Power distribution substation - ZBW -12(24) HV/LV - Ningbo Tianan (Group) CO.,Ltd. - compact / prefabricated - image - 3
Power distribution substation - ZBW -12(24) HV/LV - Ningbo Tianan (Group) CO.,Ltd. - compact / prefabricated - image - 4
Power distribution substation - ZBW -12(24) HV/LV - Ningbo Tianan (Group) CO.,Ltd. - compact / prefabricated - image - 5
Power distribution substation - ZBW -12(24) HV/LV - Ningbo Tianan (Group) CO.,Ltd. - compact / prefabricated - image - 6
Add to favorites
Compare this product

Characteristics

Fonction
power distribution
Options and accessories
prefabricated, compact
Rated voltage

0.4 kV, 10 kV, 12 kV, 20 kV, 24 kV

Current

Max.: 4,000 A

Min.: 100 A

Description

General
The ZBW series HV/LV prefabricated (combined) substation is a compact complete distribution unit integrating HV switchgear, transformer unit and LV switchgear. It is intended for power reception and distribution in commercial buildings, residential complexes, transport hubs, public facilities, industrial sites, mining operations and temporary installations.

Key characteristics
The unit provides high integration and a compact footprint, enabling reduced civil works and faster site installation. Typical HV rated options: 12 kV or 24 kV; LV rated 0.4 kV. Typical transformer range: 300–2000 kVA. HV rated currents: 630 A, 1250 A; LV rated current: 100–4000 A. The design supports ring network, dual supply and radial terminal distribution schemes.

Service Conditions
  • Ambient temperature: -25 °C to +40 °C; daily max difference < 25 °C
  • Altitude: ≤ 1000 m
  • Relative humidity: daily average ≤ 95%; monthly average ≤ 90%
  • Solar radiation: 0.1 W/cm² (wind 0.5 m/s)
  • Outdoor wind speed: ≤ 35 m/s
  • Pollution degree: III
  • Rainproof grade: 3
  • Installation slope: ≤ 3°
  • Seismic: < grade 8 (refer to project documentation)
  • Installation site: free from severe pollution, chemical corrosion, fire/explosion risk and strong vibration

Technical Data (summary)
Item | Unit | HV unit | Transformer unit | LV unit
Rated voltage | kV | 12(24) | 10(20) | 0.4
Rated current | A | 630, 1250 | — | 100–4000
Rated frequency | Hz | 50/60 | 50/60 | 50/60
Power-frequency withstand voltage (1 min, rms) | kV | To earth/phase-phase: 42(65); isolation contacts: 48(79) | 35/28(50/40) | 2.0/2.5
Lightning impulse withstand voltage (peak) | kV | To earth/phase-phase: 75(125); isolation contacts: 85(145) | 75(125) | —
Transformer rated power | kVA | — | 300–2000 | —
Short-time withstand current / duration | kA/s | 20/4 (HV) | — | 30/1 (LV)
Peak withstand current | kA | 50 (HV) | — | 63 (LV)
Number of circuits | pcs | 1–6 (HV) | 2 (transformer) | 4–30 (LV)
Protection degree | — | IP33D / IP23D (transformer enclosure)
Noise level | dB | Oil ≤ 55; Dry ≤ 65

Structure
The substation comprises three functional compartments: HV compartment, transformer compartment and LV compartment. The HV side can be configured for ring, terminal or dual supply. Transformer options: oil-immersed (low-loss) or dry-type. LV compartment: panel or cabinet type integrating distribution, lighting circuits, reactive power compensation, energy measurement and protection. Compartments include automatic lighting and optional ventilation (natural or forced) to maintain thermal conditions.

Overall dimension & typical layout
Typical 12 kV layouts, foundation and cable entry/exit drawings are provided in technical documentation; recommended layouts and foundation details are available per configuration.

Characteristics / technical specifications
  • Series: ZBW
  • Application: prefabricated HV/LV integrated substation for urban and rural distribution, commercial, residential, transport, industrial, mining and temporary sites
  • Rated HV voltage: 12 kV or 24 kV; LV rated: 0.4 kV
  • HV rated currents: 630 A, 1250 A; LV range: 100–4000 A
  • Frequency: 50/60 Hz
  • Transformer power: 300–2000 kVA
  • Short-time withstand: HV 20 kA/4 s; LV 30 kA/1 s
  • Peak withstand current: HV 50 kA; LV 63 kA
  • Protection: IP33D / IP23D (transformer enclosure)
  • Noise: oil transformer ≤ 55 dB; dry transformer ≤ 65 dB
  • LV circuits: typically 4–30 (configurable)