GeneralThe 220 kV oil-immersed power transformer uses a folding-plate tank structure adapted from 110 kV designs to provide a rational layout that simplifies site installation and inspection. Based on extensive design and manufacturing experience, the product family is engineered for low no-load and load losses, low audible noise and partial discharge, high short-circuit withstand capacity and typical short-circuit impedance ranges. Configurations include two- and three-winding units, on-load tap changers (OLTC), off-circuit tap changers and autotransformer variants.
Standard- IEC60076 (parts 1–5) Power transformers
- IEC60296 Mineral insulating oil specification
- IEC60354 Loading guide for oil-immersed transformers
- IEC60317 Insulating bushings
- Optional compliance: ANSI, IEEE, AS, GB, GOST
Features & Scope- Folding-plate tank structure for easier transport, installation and inspection
- Available configurations: 2-winding, 3-winding, autotransformer
- Tap options: off-circuit tap changer (no-load) and OLTC (on-load)
- Design focus: low no-load and load losses (levels I/II/III), low noise, reduced partial discharge, high mechanical and electrical short-circuit strength
- Applications: HV substations, grid transmission and distribution projects
Technical parameterDetailed energy-efficiency and loss tables are provided for multiple variants and rated capacities. Representative excerpts (columns separated by " | ") are shown below.
1) 220 kV, 3-phase, double-winding, off-circuit tap-changing (representative rows)Rated capacity kVA | Level I No-Load Loss kW | Level I Load Loss (75°C) kW | Level II No-Load Loss kW | Level II Load Loss (75°C) kW | Level III No-Load Loss kW | Level III Load Loss (75°C) kW | Short-circuit impedance %
31500 | 15 | 115 | 18 | 115 | 22 | 122 | 12~14
90000 | 34 | 246 | 40 | 246 | 49 | 259 | 12~14
300000 | 83 | 577 | 98 | 577 | 121 | 609 | 12~14
2) 220 kV, 3-phase, three-winding, off-circuit tap-changing (representative rows)Rated capacity kVA | Level I No-Load Loss kW | Level I Load Loss (75°C) kW | Level II No-Load Loss kW | Level II Load Loss (75°C) kW | Level III No-Load Loss kW | Level III Load Loss (75°C) kW | Set up voltage | Set down voltage
31500 | 18 | 138 | 21 | 138 | 26 | 145 | H-M:22~24; H-L:12~14; M-L:7~9
240000 | 72 | 616 | 91 | 616 | 112 | 650 | H-M:22~24; H-L:12~14; M-L:7~9
3) 220 kV, LV=66 kV double-winding, off-circuit (representative rows)Rated capacity kVA | Level I No-Load Loss kW | Level I Load Loss (75°C) kW | Level II No-Load Loss kW | Level II Load Loss (75°C) kW | Level III No-Load Loss kW | Level III Load Loss (75°C) kW | Short-circuit impedance %
31500 | 17 | 129 | 20 | 129 | 24 | 136 | 12~14
120000 | 45 | 330 | 53 | 330 | 65 | 349 | 12~14
4–6) OLTC and autotransformer variants (representative rows)Selected representative values cover OLTC-equipped double- and three-winding units and OLTC autotransformers, with detailed tap relationships (example: H-M / H-L / M-L bands) and loss figures per rated capacity (rows as above).
NotesAll tables provide rated capacities with corresponding no-load and load losses for efficiency Levels I/II/III and indicate short-circuit impedance or tap voltage bands where applicable. Values serve as reference and can be adapted to specific customer requirements and material selections.
Characteristics / technical specifications- Type: Oil-immersed power transformer, 220 kV class
- Tank: Folding-plate tank, fully enclosed
- Configurations: 2-winding, 3-winding, autotransformer
- Tap changer options: off-circuit tap changer and OLTC
- Performance indicators: no-load and load loss tables by efficiency level; typical short-circuit impedance ranges (e.g. 12~14%)
- Standards: IEC60076, IEC60296, IEC60354, IEC60317; ANSI/IEEE/AS/GB on request
- Typical rated capacities in tables: 31,500 kVA to 420,000 kVA