Product overviewThe LFT2060 refrigeration pressure transmitter uses a ceramic capacitor sensing core designed for refrigerant pressure measurement. It provides a proportional voltage output (0.5–4.5V), a wide operating temperature range and IP67 enclosure protection. Compatible with the most common refrigerants and rated for high overload and burst pressures, the LFT2060 is suited for HVACR and refrigeration system pressure monitoring.
Specifications- Model: LFT2060
- Measurement range: 0–50 Bar
- Accuracy: ±1.5% F.S (-20 to 80 °C); ±2.5% F.S (-40 to 120 °C)
- Output signal: 0.5–4.5V (proportional voltage)
- Supply voltage: 4.75–5.25 VDC
- Electrical connection: Packard, 3-wire
- Pressure connection: 7/16-20UNF (internal / external thread)
- Pressure type: Gauge pressure (G)
- Dielectric strength: 1800 VAC, 1 s
- Enclosure protection: IP67
- Working temperature: -40 to 120 °C
- Compatible refrigerants: R12, R22, R32, R134a, R404a, R407c, R410a, R502, R507
- Certifications: RoHS, CE
Features- Ceramic capacitor sensing core with high overload capability and stable thermal characteristics
- Compact dimensions and stable long‑term behaviour
- Wide operating temperature range suitable for HVACR environments
- IP67 waterproofing and anti‑condensation performance
- Proportional 0.5–4.5V output for direct interface with control electronics
NotesSealing ring default material: neoprene rubber. Alternative sealing materials available on request to match specific refrigerants or media.
Technical specifications (summary)- Overload pressure: 2× rated pressure
- Burst pressure: 3× rated pressure
- Electrical wiring: 3‑wire Packard connector
- Typical applications: refrigeration systems, chillers, HVACR pressure monitoring