PCE-28.SMART pressure transmitter is applicable to the measurement of the pressure, underpressure and absolute pressure of gases, vapours and liquids. The active sensing element is a piezoresistant silicon sensor separated from the medium by a diaphragm and by specially selected type of manometric liquid.
Communication
The communication standard for data interchange with the transmitter is the Hart protocol.
Communication with the transmitter is carried out with:
– a KAP-03, KAP-03Ex communicator
– some other Hart type communicators,(*)
– a PC using an HART/U
The data interchange with the transmitter enables users to:
identify the transmitter
configure the output parameters:
- measurement units and the values of the start points and end points at the measurement range
- damping time constant
- conversion characteristic (inversion, user's non-linear characteristic)
read the currently measured pressure value of the output current and the percentage output control level
force an output current with a set value
calibrate the transmitter in relation to a model pressure