Type 3 surge arrester MLPCA1-230L
type 2outdoorfor electrical installations

Type 3 surge arrester - MLPCA1-230L - CITEL - type 2 / outdoor / for electrical installations
Type 3 surge arrester - MLPCA1-230L - CITEL - type 2 / outdoor / for electrical installations
Add to favorites
Compare this product

Characteristics

Type
type 3, type 2
Applications
outdoor, for electrical installations
Other characteristics
gas discharge tube, hard-wired, compact, AC, wall-mount, with fault indication, single-phase, thermoplastic, varistor
Voltage

Max.: 240 V

Min.: 220 V

Primary current

Max.: 10 A

Min.: 10 A

Open circuit voltage

Max.: 10 kV

Min.: 10 kV

Description

Product
  • Compact Type 2 hard-wired surge protector
  • Model: MLPCA1-230L
  • Part Number: 835261


Key features
  • Type 2 (or 3) single-phase surge protector
  • Compact design
  • Wall or plate mounting
  • Status indicators (LED)
  • IP65
  • AC disconnection in case of end of life


Description
The MLPCA series Type 2 (or 3) surge protectors are designed to provide effective protection for sensitive equipment in coordination with a main installation surge protector. These devices use a compact, economical varistor-based topology to provide a suitable discharge capability for secondary protection applications.

Available documents (names only)
  • Datasheet
  • CITEL_Certif_EU_MLPC_MLPX.pdf
  • CITEL_Certif_UKCA_MLPC_MLPX.pdf
  • Installation Manual
  • Tender specifications


Technical specifications
  • SPD type (IEC): 2+3
  • Network: 220-240 V Single-phase
  • AC system: TT-TN
  • Nominal line voltage (Un): 230 V
  • Max. AC operating voltage (Uc): 320 Vac
  • Max. load current @25°C (IL): 10 A
  • Temporary Over Voltage (TOV) - 5 sec: 335 Vac withstand (without disconnection)
  • Temporary Over Voltage (TOV) - 120 min: 440 Vac disconnection (without disconnection or with safety disconnection)
  • Operating current (Ic) continuous at Uc: < 1 mA
  • Follow current: None
  • Nominal discharge current (In) 15 x 8/20 µs impulses: 5 kA
  • Max. discharge current per pole (Imax) @ 8/20 µs: 10 kA
  • Total Maximum discharge current (Imax Total) @ 8/20 µs: 20 kA
  • Withstand on Combination waveform IEC 61643-11 (Uoc): 10 kV
  • Withstand on overvoltages IEEE C62.41.1: 10 kV / 10 kA
  • Protection mode(s): Common/Differential mode
  • Protection level (Up) @ In (8/20µs): 1.5 kV
  • Protection level L/N @ In (Up L/N): 1.5 kV
  • Protection level L/PE @ In (Up L/PE): 1.5 kV
  • Admissible short-circuit current (Isccr): 10 000 A
  • Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 ed.5
  • Technology: MOV + GDT
  • Connection to network: Cable with 4-wire of 1.5 mm²
  • Mounting: Wall or plate
  • Housing material: Thermoplastic UL94 V-0
  • Operating temperature: -40 / +85 °C
  • Protection rating: IP65
  • Failsafe mode: Disconnection and AC line cut-off
  • Thermal disconnector: Internal
  • Installation ground fault breaker: Type 'S' or delayed
  • Disconnection indicator: Green LED OFF and line cut off
  • Operating indicator: Green LED ON
  • Dimensions: See diagram
  • Weight: 0.142 kg

Catalogs

No catalogs are available for this product.

See all of CITEL‘s catalogs
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.