Description- Type 2+3 surge protector with integrated electrostatic protection
- Designed for Class II LED lighting systems
- Improved coordination with internal MOV
- Electrostatic protection (N / Functional Earth)
- No residual leakage current to protective earth
- Very compact, plate mount design
- Spring terminal or screw terminal connection (as specified)
- Status indicator and end-of-life AC disconnection
- Compliant with IEC/EN 61643-11
Electrical PropertiesSPD type (IEC): 2+3
Isolation class: II
Network: 220-240 V single-phase
AC system: TT-TN
Max. AC operating voltage (Uc): 320 Vac
Max. load current @25°C (IL): 5 A
Temporary Over Voltage (TOV) - 5 s (without disconnection): 335 Vac withstand
Temporary Over Voltage (TOV) - 120 min (with disconnection): 440 Vac disconnection
Residual current (leakage to ground) (Ipe): None
Nominal discharge current (In) 15 x 8/20 µs impulses: 5 kA
Max. discharge current per pole (Imax) @ 8/20 µs: 10 kA
Total max. discharge current (Imax Total) @ 8/20 µs: 20 kA
Combination waveform withstand (IEC 61643-11) (Uoc): 10 kV
Withstand on overvoltages IEEE C62.41.1: 10 kV / 10 kA
Protection level @ In (Up): 1.5 kV
Admissible short-circuit current (Isccr): 10 000 A
Electrostatic protection level (Uesp): 0.5 kV
Electrostatic protection mode: N / Functional Earth
Mechanical PropertiesConnection to network: 2 screw terminals opposite side in/out - wire max 2.5 mm²
Mounting: On plate
Housing material: Thermoplastic UL94 V-0
Operating temperature (Tu): -40 to +85 °C
Protection rating: IP20
Failsafe mode: Thermal disconnection and AC line cut-off
Disconnection indicator: Green LED OFF and AC network cut-off
Operating indicator: Green LED ON
Dimensions: See technical diagram
Weight: 0.035 kg
StandardsStandards compliance: EN 61643-11 / IEC 61643-11
DisconnectorThermal disconnector: Internal
Installation ground fault breaker: Type 'S' or delayed
Schematics / DiagramsProduct includes schematic and diagram images (see technical diagrams)
Technical characteristics- Brand: CITEL
- Reference / Model: MLPC2-230L-R/ESP2
- Part Number: 832217
- SPD type: 2+3
- Isolation class: II
- Network: 220-240 V single-phase
- AC system: TT-TN
- Uc (Max. AC operating voltage): 320 Vac
- IL (Max. load current @25°C): 5 A
- In (Nominal discharge current): 5 kA (15 x 8/20 µs)
- Imax (Max. discharge current per pole): 10 kA (8/20 µs)
- Imax Total (Total max discharge current): 20 kA (8/20 µs)
- Combination waveform withstand (IEC 61643-11): 10 kV
- IEEE C62.41.1 withstand: 10 kV / 10 kA
- Up (Protection level @ In): 1.5 kV
- Uesp (Electrostatic protection level): 0.5 kV
- Isccr: 10 000 A
- Connection: 2 screw terminals opposite side in/out, wire max 2.5 mm²
- Mounting: On plate
- Housing: Thermoplastic UL94 V-0
- Operating temperature: -40 to +85 °C
- Protection rating: IP20
- Failsafe: Thermal disconnection and AC line cut-off
- Disconnection indicator: Green LED OFF and AC network cut-off
- Operating indicator: Green LED ON
- Weight: 0.035 kg
- Thermal disconnector: Internal
- Installation ground fault breaker: Type 'S' or delayed
- Standards: EN 61643-11 / IEC 61643-11