High-accuracy turbidity sensor DAW-TR20-S
Modbus RTURS-4854-20mA

High-accuracy turbidity sensor - DAW-TR20-S - DABECO Co.,Ltd - Modbus RTU / RS-485 / 4-20mA
High-accuracy turbidity sensor - DAW-TR20-S - DABECO Co.,Ltd - Modbus RTU / RS-485 / 4-20mA
Add to favorites
Compare this product

Characteristics

Other characteristics
high-accuracy, Modbus RTU, RS-485, for water, 4-20mA

Description

Overview This online turbidity analyzer is engineered for continuous drinking-water quality monitoring using 90° laser scattering (660 nm).
Scattered light from suspended particles is measured and converted to turbidity values via calibration. The unit offers an ultra-low detection limit (0.005 NTU), high precision (±2% or ±0.02 NTU), a circulatory flow-through path, anti-fouling flow channel and integrated de-bubbling for stable, repeatable readings.
IP68 sensor protection, RS-485 Modbus-RTU digital communication and optional 4–20 mA analog output enable integration into SCADA/DCS systems. Operates on DC 9–28 V and within -5 to 45 °C. Recommended sample flow is 500 mL/min (range 100–1000 mL/min).

Industry Applications
  • Water treatment plants and process control
  • Secondary (building) water supply systems
  • Distribution network endpoints (tap water monitoring)
  • Direct drinking water facilities and point-of-use monitoring
  • Membrane-filtered and RO systems
  • Swimming pool and recreational water monitoring
  • Surface water monitoring and intake protection
  • Any application requiring low-level turbidity detection

Product Features
  • Ultra-low detection limit: 0.005 NTU for early contamination detection
  • High precision: laser light source and high-precision electronics for stable results
  • Stable operation: circulatory flow-through design minimizes measurement drift
  • Anti-fouling water path: flow-channel geometry reduces particle adherence
  • Integrated de-bubbling: maintains accuracy in aerated or variable-flow conditions
  • Industrial interfaces: RS-485 Modbus-RTU and optional 4–20 mA for system integration

Technical Specifications
  • Model: DAW-TR20-S
  • Measurement principle: 90° laser scattering, 660 nm laser
  • Range: 0–1 / 20 / 100 NTU
  • Resolution: 0.0001 NTU (<1 NTU) / 0.001 NTU (≥1 NTU)
  • Limit of detection: 0.005 NTU
  • Accuracy: ±2% or ±0.02 NTU (whichever is greater) using Formazin primary standard at 25 °C
  • Sample flow: 100–1000 mL/min (recommended 500 mL/min); recommended flows: membrane-filtered 100–300 mL/min, tap water 300–600 mL/min
  • Power supply: DC 9–28 V; Power consumption: 5 W (peak)
  • IP rating (sensor): IP68; Mounting: wall-mounted
  • Operating temperature: -5 to 45 °C; Storage: -20 to 60 °C; Humidity: 5%–95% RH non-condensing
  • Connections: inlet φ6 mm hose; outlet/drain φ10 mm hose
  • Digital output: RS-485 Modbus-RTU; optional 4–20 mA
  • Dimensions (W×H×D): 174 × 269 × 99 mm; Weight: approx. 1.2 kg
  • Note: Product improvements may change specifications; YuanGan reserves the right to modify parameters.