Product features- 0-20 mA / 4-20 mA / 0-10 V / 2-10 V / 0-5 V inputs
- large, 5 digit LED display (101 mm character height)
- adjustable brightness
- readable even at a 50 m distance
- menu driven setting, via front panel switches
- 0.03% accuracy
- 24 VDC ±10% or 230 V AC/DC ±10% power supply
- 656 × 150 × 45 mm wall mount instrument
Product descriptionThe
DT4226 … Process Indicator enable linear process variables (0-20 mA / 4-20 mA / 0-10 V / 2-10 V / 0-5 V) to be displayed in engineering units on the place of installation. Any optional display range can be assigned to the input signal range.
Large 5 digit, 101 mm height LED display with adjustable brightness make process value easily visible at a 50 m distance.
The functional parameters can be set by membrane push-buttons on the front panel of the device, through a simple menu system: input selection, averaging of input signals, scaling, display refresh rate, etc. The settings are protected by a two-level password against unauthorised manipulation.
The instruments has two power supply versions: 24 VDC ±10% (DT4226 …) or 230 V AC/DC ±10% (DT4226 … PS)
The DT4226 … is housed in a metal case with IP40 protection for installation on a flat surface (e.g. wall).
Technical specificationSafety data: The inputs and the connection terminals of the supply voltages are isolated from each other, the isolation is in compliance with the
standard EN 61010-1, taking into consideration the following:
- Pollution level: 2
- Measurement category: II
Input parameters:- Input signal: DC current or DC voltage
- Measurement range: 0-20 mA / 4-20 mA / 0-10 V / 2-10 V / 0-5 V
- Overrange: ±50 mA (current input), ±200 V (voltage input)
Measuring parameters:- Characteristics: linear
- Sampling: 12 measurement / sec.
- Number of averaged samples: 1 / 2 / 4 / 8 / 16 / 32 / 64 (adjustable)
- Error of displayed value: 0.03% (Ta = 23 ˚C ±2 ˚C)
- Temperature-coefficient: 40 ppm / ˚C
Display:- Display unit: 5 digit LED
- Character height: 101 mm
- Display color: red
- Brightness: adjustable between 10% - 100% in increments of 10%
- Display: 5 digit (+values), 4 digit (-values), negative sign, decimal point
Manual controls:- Manual controls: 3 membrane push-buttons on the front cover
Power supply:- Supply voltage: 24 VDC ±10% (DT4226 …); 230 V AC/DC ±10% (DT4226 ... PS)
- Consumption: 5 W (DT4226 …); 6 W (DT4226 ... PS)
Ambient conditions:- Operating temperature range: 0 - +50 °C
- Storage temperature range: -25 - +70 °C
- Relative humidity: 90% (max., non condensing)
- Place of installation: indoor
Electromagnetic compatibility (EMC) accordance with the standard EN 61326-1- Immunity: industrial area
- Noise emission: Group 1, Class B
General data:- Housing: wall mount instrument
- Connection: GM 209 NJ valve connector (power supply)
- GDM 2009 valve connector (signal input)
- Connection cable: 0.25-1.5 mm2 (max.)
- Dimensions: 656 × 150 × 45 mm (width × height × depth)
- Weight: 3.4 kg
- Protection: IP40
Detailed information see in operating instructions. The Manufacturer maintans the right to change the technical data!