Current transformer LB7-72.5
instrumentmeasurementimmersed

Current transformer - LB7-72.5 - Dowei Electric - instrument / measurement / immersed
Current transformer - LB7-72.5 - Dowei Electric - instrument / measurement / immersed
Add to favorites
Compare this product

Characteristics

Type
current, instrument, measurement
Configuration
immersed
Applications
industrial, for industrial applications, for industrial use, for electrical networks, protection, for energy meters, substation
Electrical characteristics
single-phase
Mounting
floor-standing
Norms
IEC, UL, ANSI, TUV
Other characteristics
protection, control, high-accuracy, oil-immersed, multi-winding
Primary voltage

72.5 kV

Secondary voltage

Max.: 220 V

Min.: 110 V

Description

• IEC 61869, ANSI/IEEE C57.13, NEMA
• ISO 9001, KEMA, CESI, CE, TUV, UL, ASTA
• Seismic design, ETGI-1.020, IEEE Std 693, NCh2369
• Structural design, ASTM A325, ANSI/AISC 360, AWS D1.1
• High altitude correction per IEC 61869 & IEEE C57, ~ 5000m
• High Quality Paper-Oil Insulation, Mineral oil (No PCB), Hermetically Sealed
• Special accuracy classes PR, PX, PXR, TPX, TPY, TPZ or C 100-800 (IEEE), etc..

72.5 kV Current Transformer (Hair-pin Type) is a high-voltage instrument transformer used in transmission and sub-transmission substations to accurately measure high primary currents and provide isolated secondary currents for protection, metering, monitoring, and control. The hair-pin type incorporates a single U-shaped (hair-pin) primary conductor that passes through the magnetic core, offering a simple, robust, and reliable design.

Working Principle

A 72.5 kV hair-pin type current transformer operates according to the principle of electromagnetic induction.

When alternating current flows through the integral hair-pin primary conductor, it generates an alternating magnetic flux in the transformer core. This flux induces a proportional current in the secondary winding.

Construction
A typical 72.5 kV hair-pin current transformer includes:
·Integral U-shaped copper or aluminum primary conductor
·High-permeability toroidal magnetic core
·One or more secondary windings
·Porcelain or composite hollow insulator
·Oil-paper or SF6 insulation system (depending on manufacturer)
·Expansion chamber or oil conservator (for oil-filled designs)
·Secondary terminal box
·Grounding terminal
·Mounting pedestal
·Stainless steel nameplate

Features
·Integral single-turn hair-pin primary.
·Excellent measurement accuracy.
·Suitable for both metering and protection.
·Multiple secondary cores available for different functions.
·High thermal and dynamic short-circuit withstand capability.
·Outdoor weather-resistant construction.
·Low partial discharge levels.
·Long operating life with minimal maintenance.

Typical Ratings
·Highest system voltage: 72.5 kV
·Rated frequency: 50 or 60 Hz
·Primary current: 100–4000 A
·Secondary current: 1 A or 5 A
·Metering accuracy class: 0.1, 0.2, 0.2S, 0.5, 0.5S
·Protection accuracy class: 5P10, 5P20, 10P10, PX, TPY
·Rated burden: 10–60 VA
·Lightning impulse withstand: Typically 325 kV
·Power-frequency withstand: Typically 140 kV (1 min)
·Installation: Outdoor AIS

Advantages
·High accuracy over a wide current range.
·Compact primary conductor design.
·Excellent mechanical strength.
·Reliable insulation for 72.5 kV systems.
·High short-circuit withstand capability.
·Multiple secondary cores support separate metering and protection circuits.
·Long service life under outdoor operating conditions.

Limitations
·Cannot be serviced while energized.
·Larger and heavier than medium-voltage resin-cast CTs.
·Oil-filled units require periodic inspection for oil condition and seals.
·The secondary winding must never be open-circuited while the primary is energized, as hazardous voltages can be induced.

Applications
A 72.5 kV hair-pin type current transformer is commonly used in:
·66 kV and 72.5 kV transmission substations
·Utility switching stations
·Power transformer bays
·Transmission line feeder bays
·Busbar protection schemes
·Circuit breaker protection
·Revenue metering
·Industrial high-voltage substations
·Renewable energy grid interconnections

A 72.5 kV Hair-pin Type Current Transformer is a dependable instrument transformer for 66/72.5 kV outdoor air-insulated substations (AIS). Its integral single-turn primary conductor provides high mechanical strength, excellent accuracy, and reliable performance for protection relays, energy metering, fault recording, and supervisory control systems under demanding transmission network conditions.
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.