Characteristics

Mounting
bracket-mounted
Other characteristics
public, horn, IP66, explosion-proof, for hazardous areas, IP67, fire-resistant, robust, ATEX
Sound level

123 dB

Input power

Max.: 25 W

Min.: 1 W

Description

Product overview
The D1xL2F is a 25W PA loudspeaker with a re-entrant flare horn designed for high SPL public address and signaling in hazardous areas. The unit is housed in a marine-grade, corrosion-proof LM6 aluminium enclosure (Type 4/4X, IP66/67) suitable for Class I & II Div 1 and Zone 1, 20 and 21 explosion-proof applications.

Description
The flare re-entrant horn is high-impact, fire-retardant thermoplastic and is field replaceable. The driver uses a standard 1 3/8"-18 male thread coupling. All models feature triple cable entries with duplicated terminals. A large termination chamber and a threaded flameproof joint on the cover simplify installation and routine maintenance.

Features
  • Multiple transformer tappings (25/70/100V options)
  • Ratchet-adjustable 316 stainless steel mounting bracket
  • Triple cable entries and duplicated cable terminations
  • Robust marine-grade aluminium enclosure with chromate & powder coat finish (ISO 12944-6)
  • UL 1480 and CAN/ULC-S541 fire alarm & signaling speaker listings

Part codes / Options
Product type: D1xL2 — D1xL2 25W Loudspeaker. Horn type: F — Flare re-entrant horn. Type options: V100 (100V transformer), V070 (70V), V725 (25V/70V), R008 (8 Ω low impedance), R016 (16 Ω low impedance).
Cable entry options: A/B/C/D/F/G — various M20/M25 and NPT adaptor configurations; stopping plugs supplied (excluding adaptors). Stopping plug/adaptor material: Brass / Nickel plated brass / Stainless steel. Bracket: A4 316 stainless steel (equipment tag optional). Product versions: A — UL, cUL, IECEx, ATEX, CSFM, INMETRO, DNV; D — Class II UL/cUL (some transformer options excluded). Standard and custom configurations available. Enclosure colour: Red or Grey (special colours on request).

Approvals
  • UL / cUL (File ref: E230764)
  • IECEx (IECEx ULD 19.0008X)
  • ATEX (DEMKO 19 ATEX 2141X)
  • CSFM listing (7136-2279:0504)
  • UKCA (UL21UKEX2132X)
  • INMETRO (IEx 24.0158X)
  • DNV (TAA00003KC)

Technical specifications
  • Rated power: 25 Watts RMS
  • Version A SPL: 104dB ±3dB @ 1W @ 1m (Pink); 119dB ±3dB @ 25W @ 1m (Rated); 123dB(A) @ 1m at 1.3kHz (Max)
  • Version D SPL: 89dB ±3dB @ 1W @ 1m (Pink); 98dB ±3dB @ 25W @ 1m (Rated); 108dB(A) @ 1m at 1.3kHz (Max)
  • 25/70V line tappings (version A): 25W / 12.5W / 6W / 2W / 1W (impedances detailed in datasheet)
  • 70V tappings (low impedance option listed): 25W / 12.5W / 6W / 2W
  • 100V tappings: 25W / 12.5W / 6W / 2W
  • Low impedance options: 8 Ω or 16 Ω
  • Q Factor: 3.1 @ 500Hz; 2.8 @ 1kHz; 6.4 @ 2kHz; 13.2 @ 4kHz; 13.8 @ 8kHz
  • Directivity Index: 4.9 @ 500Hz; 4.5 @ 1kHz; 8.1 @ 2kHz; 11.2 @ 4kHz; 11.4 @ 8kHz
  • Frequency range: 400Hz to 8,000Hz
  • DC line monitoring: 2.2µF capacitor (transformer); 470µF capacitor (low impedance)
  • Ingress protection: EN60529: IP66/67; UL50E / NEMA250: 4/4X/3R/13
  • Enclosure material: Marine grade LM6 aluminium alloy
  • Enclosure finish: Chromate & powder coated — ISO 12944-6 CX, C5VH & C5H
  • Standard cable entries: 1 × 1/2" NPT & 2 × M20 (thread adaptors available)
  • Terminals: 0.5–2.5mm² (20–14 AWG), duplicated
  • Grounding stud: M5
  • Enclosure volume: <2 litres
  • Installation temperature (version A): NEC: -55° to +85°C; CEC/IECEx/ATEX: -55° to +75°C
  • Installation temperature (version D): NEC Class Div: -40° to +70°C; NEC Class Zone / CEC: -55° to +75°C
  • Storage temperature: -55° to +85°C
  • Relative humidity: 95% (additional tropicalisation recommended for high RH & high ambient temps)
  • MTBF (V100/V070/V725): 630.69 years / 5,524,861 hours (MIL-217)
  • MTBF (R008/R016): 830.22 years / 7,272,727 hours (MIL-217)
  • Weight: Line versions (100V/70V/25/70V): 4.5 kg; Low impedance: 4.2 kg