GeneralThe VT19-12/24 indoor AC high-voltage vacuum circuit breaker is a switching device for 12 kV and 24 kV power systems that provides control and protection for electrical equipment in industrial plants, mines, power stations and substations. It is suitable for frequent switching at rated current and repeated interruption of short-circuit currents. The breaker features an integrated operating mechanism and body with a front-and-back split structure and reliable interlocks; it is available as fixed, handcart or withdrawable (trolley) installations.
Standards- IEC 62271-100:2008 — High-voltage switchgear and controlgear
- GB/T 1984-2014 — AC high-voltage circuit breakers
- JB/T 3855-2008 — 3.6~40.5 kV indoor AC high-voltage vacuum circuit breakers
- DL/T 403-2000 — Technical specifications for ordering 10–40.5 kV HV vacuum circuit breakers
Type designationVT19 series: VT19-12 for 12 kV variants; VT19-24 for 24 kV variants. Multiple mechanical variants and cabinet-width options are available for each rating.
Service Conditions- Ambient temperature: +40°C to -15°C
- Relative humidity: daily average ≤ 95%; monthly average ≤ 90%
- Daily average vapor pressure ≤ 2.2×10⁻³ MPa; monthly average ≤ 1.8×10⁻³ MPa
- Altitude: ≤ 1000 m (VT19-12/24); special versions up to 2000 m
- Earthquake intensity: ≤ grade 8
- Installation site: free from water accumulation, explosion hazard, serious pollution, chemical corrosion and severe vibration
- Custom designs available for special service conditions
Technical ParametersRated voltage: 12 / 24 kV
Rated frequency: 50/60 Hz
1 min power-frequency withstand voltage (phase-to-phase/phase-to-earth): 75 kV (12 kV) / 125 kV (24 kV)
Rated lightning impulse withstand voltage (peak): 42 kV (12 kV) / 65 kV (24 kV)
Rated operation sequence: O-0.3s-CO-180s-CO
Circuit breaker ratings and breaking capability (summary)- Rated current options (A): 630, 1250, 1600, 2000, 2500, 3150, 4000 (4000 A may require forced cooling)
- Rated short-circuit breaking current (kA): typical options 20, 25, 31.5, 40, 50 depending on configuration
- Rated short-circuit making current (peak kA): examples 50 / 63 / 80 / 100 / 125 depending on variant
- Rated duration of short circuit: commonly 4 s
- Electrical breaking duty: multiple interruptions possible per table (application dependent)
Mechanical characteristic parameters (selected)- Open contact clearance: 9 ±1 mm (12 kV); 13 ±1 mm (24 kV)
- Over-travel: 3.5 ±0.5 mm
- Three-phase opening/closing asynchronous: ≤ 2 ms
- Contact bounce time on closing: ≤ 2 ms (≤ 3 ms for highest ratings)
- Contact pressure (N): ranges per interrupting rating (e.g. 2000±200 to 5500±200)
- Average opening speed (m/s): 0.9–1.3 (12 kV); 1.1–1.6 (24 kV)
- Average closing speed (m/s): 0.4–0.8 (12 kV); 0.6–1.0 (24 kV)
Opening and closing timeClosing time (ms): 30–70 (typical for 12 & 24 kV variants)
Opening time (ms): 15–45 (typical)
Design and construction features- Integrated operating mechanism and breaker body with front-and-back split structure
- Reliable mechanical and electrical interlocks
- Mounting variants: fixed, handcart (trolley) or withdrawable with different travel distances and cabinet widths
- Multiple mechanical/outline dimension variants for phase spacing and mounting per rated current
Characteristics / Technical specifications- Model series: VT19
- Nominal system voltages: 12 kV and 24 kV
- Rated frequency: 50/60 Hz
- Withstand voltages: 1 min 75 kV (12 kV) / 125 kV (24 kV); lightning impulse 42 kV (12 kV) / 65 kV (24 kV)
- Operation sequence: O-0.3s-CO-180s-CO
- Rated current range: 630 A to 4000 A (application dependent)
- Breaking capability: 20 kA to 50 kA (variant dependent)
- Mechanical life: typically 30,000 operations
- Variants: fixed, handcart, withdrawable; multiple cabinet widths and phase spacings available
- Standards compliance: IEC62271-100, GB/T1984-2014, JB/T3855-2008, DL/T403-2000