Vacuum circuit breaker VT19-40.5
spring operatedhigh-voltagefor three-phase

Vacuum circuit breaker - VT19-40.5 - Ningbo Tianan (Group) CO.,Ltd. - spring operated / high-voltage / for three-phase
Vacuum circuit breaker - VT19-40.5 - Ningbo Tianan (Group) CO.,Ltd. - spring operated / high-voltage / for three-phase
Vacuum circuit breaker - VT19-40.5 - Ningbo Tianan (Group) CO.,Ltd. - spring operated / high-voltage / for three-phase - image - 2
Vacuum circuit breaker - VT19-40.5 - Ningbo Tianan (Group) CO.,Ltd. - spring operated / high-voltage / for three-phase - image - 3
Vacuum circuit breaker - VT19-40.5 - Ningbo Tianan (Group) CO.,Ltd. - spring operated / high-voltage / for three-phase - image - 4
Vacuum circuit breaker - VT19-40.5 - Ningbo Tianan (Group) CO.,Ltd. - spring operated / high-voltage / for three-phase - image - 5
Add to favorites
Compare this product

Characteristics

Type
vacuum, spring operated
Electrical characteristics
short-circuit, high-voltage, for three-phase
Operating mode
high-voltage, manually-operated
Applications
for power generation installations, for substations
Number of poles
3-pole
Other characteristics
indoor, fixed, trolley-mounted
Primary current

Max.: 3,150 A

Min.: 630 A

VAC

40.5 kV

Description

General
The VT19-40.5 indoor high-voltage vacuum circuit breaker is a control and protection switching device for three-phase 50/60 Hz, 35 kV power systems. It is intended for industrial, mining, power plant and substation switchgear and is suitable for frequent operations and multiple short-circuit interruption duties. It is available as handcart (withdrawable) or fixed versions.

Standards
The breaker is designed to meet GB1984 (HV AC circuit breaker), JB3855 (HV AC vacuum circuit breaker) and relevant IEC standards. It includes reliable mechanical and electrical interlocks and can be supplied in handcart or fixed configurations.

Service conditions
  • Ambient temperature: +40°C to -15°C
  • Relative humidity: daily average ≤ 95% (daily vapor pressure ≤ 2.2×10⁻³ MPa); monthly average ≤ 90% (monthly vapor pressure ≤ 1.8×10⁻³ MPa)
  • Altitude: ≤ 2000 m (standard, suitable for VT19-40.5EP)
  • Earthquake intensity: ≤ grade 8
  • Installation site: free from water drops, inflammable/explosive substances, chemical corrosive gases and severe vibration
  • Special service conditions: consult manufacturer


Technical parameters
  • Type: VT19-40.5
  • Rated voltage: 40.5 kV
  • Rated frequency: 50/60 Hz
  • Rated lightning impulse withstand voltage: 185 kV
  • Rated 1 min power-frequency withstand voltage: 95 kV
  • Rated operation sequence: O-0.3s-CO-180s-CO
  • Available rated currents (A): 630; 1250; 1600; 2000; 2500; 3150 (model dependent)
  • Rated short-circuit breaking current: 20 / 25 / 31.5 kA (depending on configuration)
  • Rated short-circuit making current (peak): up to 80 kA
  • Rated short-circuit duration: 4 s
  • Rated breaking times of short circuit: 20 or 30 (depending on configuration)
  • Mechanical life: 10,000 operations


Mechanical characteristics
  • Applicable to 40.5 kV: contact clearance (open) 18 ± 1 mm
  • Over-travel: 4 ± 0.5 mm
  • Three-phase opening/closing asynchronous: ≤ 2 ms
  • Closing contact bounce time: ≤ 3 ms
  • Contact closing pressure: for 20 kA / 25 kA / 31.5 kA → 2000 ± 200 N, 2700 ± 200 N, 3100 ± 200 N respectively
  • Average opening speed: 1.8 ± 0.2 m/s; average closing speed: 0.8 ± 0.2 m/s


Opening and closing time
  • 40.5 kV: Closing time = 30–70 ms; Opening time = 15–50 ms


Outline dimension notes
  • Handcart type: travel distance ≈ 615 ± 2 mm. Rated current / short-circuit ratings indicated on dimensional drawings.
  • Fixed type: similar rated current options; short-circuit breaking current up to 31.5 kA depending on model.
  • Phase spacing examples (mm) by current configuration: Φ35, Φ49, Φ55, Φ79, Φ109 (refer to drawings for exact values).


Structure
  • Main structure: integrated design with operating mechanism and main conductive circuit arranged front/rear. Pole options: high-strength nylon embedded pole, APG epoxy-sealed pole, composite insulated pole; solid/composite poles reduce dust on the arc-extinguishing chamber and protect the vacuum interrupter.
  • Operating mechanism: spring energy-storage mechanism located under the breaker, with stored-energy part, transmission, closing/opening units and tripping units (electromagnets, auxiliary switches, indicators). Front panel provides close/open button, manual energy-storage handle hole and status indicators.


Technical specifications
  • Model: VT19-40.5
  • Rated voltage: 40.5 kV
  • Frequency: 50/60 Hz
  • Lightning impulse withstand voltage: 185 kV
  • Power-frequency withstand voltage (1 min): 95 kV
  • Operation sequence: O-0.3s-CO-180s-CO
  • Rated currents: 630; 1250; 1600; 2000; 2500; 3150 A
  • Short-circuit breaking currents: 20 / 25 / 31.5 kA
  • Peak making current: up to 80 kA
  • Rated short-circuit duration: 4 s
  • Mechanical life: 10000 cycles
  • Operating temperature range: -15°C to +40°C
  • Installation altitude: ≤ 2000 m (standard)