GeneralThe VS1 (VTD6) series indoor high-voltage AC vacuum circuit breaker is designed for switchgear with rated voltages of 12 kV and 24 kV. It provides protection and control of electrical equipment in industrial plants, mining, power stations and substations and is suitable for frequent operations and multiple short-circuit interruptions.
Design and installationThe circuit breaker integrates the operating mechanism and the breaker in front and rear sub-assemblies with a reliable interlock. It is available as a fixed unit or as a withdrawable handcart unit with chassis for installation flexibility and maintenance access.
Standards- GB/T1984 — High-voltage AC circuit breaker
- DL/T403 — High-voltage AC circuit breaker
- IEC 60694 — Common specifications for high-voltage switchgear and controlgear
- IEC 62271-100 — High-voltage switchgear and controlgear — Part 100: AC circuit-breakers
Service Conditions- Ambient temperature: -15 °C to +40 °C
- Altitude: ≤ 1000 m
- Daily average relative humidity: ≤ 95%
- Monthly average relative humidity: ≤ 90%
- Daily average vapor pressure: ≤ 2.2×10⁻³ MPa
- Monthly average vapor pressure: ≤ 1.8×10⁻³ MPa
- Earthquake resistance: ≤ grade 8
- Site: no dripping, no flammable/explosive hazards, no corrosive gases, no violent vibration
Type and designationAvailable configurations: fixed type and withdrawable (handcart) type. Front-and-rear sub-assembly structure. Multiple cabinet widths and phase spacing options (typical phase spacing: 150 mm, 210 mm, 275 mm) are offered depending on model and rated current.
Technical DataBasic electrical parameters:
Rated voltage: 12 kV / 24 kV
Rated frequency: 50 / 60 Hz
1 min power-frequency withstand voltage (phase-to-phase / to earth): 42 kV (12 kV) / 65 kV (24 kV)
Rated lightning impulse withstand voltage (peak): 75 kV (12 kV) / 125 kV (24 kV)
Rated operation sequence: O-t-CO-t'-CO
Rated current options (A): 630, 1250, 1600, 2000, 2500, 3150, 4000 (model-dependent)
Rated short-time breaking current (kA): examples 20 / 25 / 31.5 / 40 / 50 (depending on model)
Rated short-circuit making current (peak kA): examples 50/63 / 80 / 100 / 125 (depending on model)
Rated short-circuit duration: 4 s
Mechanical life: typically 20000 operations (some high-current variants 10000)
Mechanical characteristicsContact distance: 9 ±1 mm (12 kV) ; 13 ±1 mm (24 kV)
Over-travel: 3.5 ±0.5 mm
Three-phase C/O asynchrony: ≤ 2 ms
Closing contact bounce time: ≤ 2 ms (≤ 3 ms at 50 kA)
Contact closing pressure (N): varies by short-circuit rating (e.g. 2000 ±200 N up to 5500 ±200 N)
Average opening speed: 0.9–1.31 m/s (12 kV) ; 1.1–1.6 m/s (24 kV)
Average closing speed: 0.4–0.8 m/s (12 kV) ; 0.6–1.0 m/s (24 kV)
Operating timesClosing time: 30–70 ms
Opening time: 15–45 ms
Coils and locking electromagnetOpening coil power: 368 W, rated voltage 220/110 V
Closing coil power: 368 W, rated voltage 220/110 V
Locking electromagnet power: 4.8 W, rated voltage 220/110 V
Energy charging motorRated voltage: 220/110 V; Power: typically 70 W (for 20–40 kA classes), 90 W for 50 kA. Charging time ≤ 15 s for applicable current classes.
Outline dimensions and configurationsOutline drawings and dimension tables provided for fixed and withdrawable types at 12 kV and 24 kV. Cabinet widths and trolley travel distances vary by configuration; contact and phase spacing dimensions depend on rated current and cabinet width.
Notes / Specifications- Selected parameters (rated currents, short-circuit ratings, contact dimensions, phase spacing, mechanical parameters, coil and motor data) depend on exact model and configuration.
- Model 4000 A may require forced-air cooling in some variants.
- Refer to dimensional drawings and technical tables when selecting fixed vs withdrawable and 12 kV vs 24 kV versions.