GeneralThe VTD5-(12/24)40.5 vacuum circuit breaker is designed for GIS applications with a horizontal mounting arrangement. It uses a sealing flange plate as the reference installation interface and an electric spring operating mechanism with three-pole linkage, operable electrically or manually. For rated currents ≥2000 A a high‑strength insulating plate holds the vacuum interrupter on the flange; for currents <1600 A an APG enclosed structure fixes the vacuum interrupter (VXG) to the flange via a fixing plate. Dynamic contact motion is transmitted via the insulating rod and stainless‑steel sealing bellows that connect the crank arm and mechanism. Secondary cables terminate at an aerial socket for simplified secondary wiring. The breaker is capable of opening at rated current, interrupting short‑circuit currents and closing on short‑circuit conditions.
Main technical parametersItem | Unit | Parameter
Rated voltage | kV | 12, 24, 40.5
Rated current | A | 630, 1250, 1600, 2000, 2500, 3150
Rated short‑circuit breaking current | kA | 20, 25, 31.5
Rated insulation level — 1 min power‑frequency withstand voltage (r.m.s) | kV | 42 (12 kV), 65 (24 kV), 95 (40.5 kV)
Rated insulation level — lightning impulse withstand voltage (peak) | kV | 75 (12 kV), 125 (24 kV), 85 (40.5 kV)
Rated short‑time withstand current (4 s) | kA | 20, 25, 31.5
Rated peak short‑time current / making current | kA | 50, 63, 80
Rated operating sequence | / | O - 0.3s - CO - 180s - CO
Mechanical life | operations | 10,000
Outline dimension and structure diagramOutline and structure diagrams are provided in the product documentation to verify mounting clearances and interfaces; refer to associated technical drawings for installation.
Maintenance- Annual power‑off inspection and maintenance to verify correct operation.
- Perform power‑frequency withstand test on the tube, measure vacuum level and record results.
- Perform power‑frequency withstand test on insulating components.
- Measure contact gap, contact travel and mechanical characteristics; record results.
- Inspect connecting bolts, nuts and adjustable parts for loosening; check small screws on auxiliary switch levers and locking nuts on moving conductor rods.
- Check retaining rings, pins and rotating joints for loosening or disengagement; apply grease to rotating and sliding parts.
- For breakers >1600 A perform DC resistance test on each pole and record results.
- If tube replacement is required follow the product manual; after replacement perform mechanical characteristic and withstand voltage tests.
- After annual inspection and before commissioning carry out 8–10 no‑load operations to verify function.
Characteristics / technical specifications- Model series: VTD5 series
- Application: GIS (gas‑insulated switchgear)
- Configuration: horizontal; sealing flange plate as installation interface
- Operating mechanism: electric spring mechanism, three‑pole linkage, electric or manual operation
- Rated voltages: 12 kV, 24 kV, 40.5 kV
- Rated currents: 630 A, 1250 A, 1600 A, 2000 A, 2500 A, 3150 A
- Short‑circuit breaking currents: 20 kA, 25 kA, 31.5 kA
- Short‑time withstand (4 s): 20 kA, 25 kA, 31.5 kA; peak/making currents: 50 kA, 63 kA, 80 kA
- Insulation withstand voltages (1 min, rms): 42 / 65 / 95 kV (12/24/40.5 kV)
- Lightning impulse withstand (peak): 75 / 125 / 85 kV (12/24/40.5 kV)
- Operating sequence: O - 0.3s - CO - 180s - CO
- Mechanical life: 10,000 operations