GeneralThe VTD9-12D indoor high-voltage AC vacuum circuit breaker is an indoor switching device designed to close, carry and break current under normal circuit conditions, to carry specified overcurrents for specified durations, and to make and break current under abnormal conditions such as short-circuits. It is intended for three-phase AC 50/60 Hz, 12 kV power systems and is used as a control and protection unit in industrial, mining, photovoltaic and wind power, residential and urban distribution applications.
Detail introductionVacuum circuit breakers are well suited to frequent switching operations at rated currents and to applications where short-circuit currents are interrupted repeatedly. The three poles are mounted longitudinally on a side-mounted frame and incorporate isolating switches, the breaker poles, earthing switches and operating mechanisms in a side-mounted structure. The design emphasizes compactness, modularization and low maintenance, enabling installation in confined spaces such as distribution rooms, prefabricated substations and underground garages.
Quality standardThe product is developed and produced to comply with current standards and quality systems. It meets or is designed in accordance with applicable versions of:
- IEC 62271-1 — High-voltage switchgear and controlgear — Part 1
- IEC 62271-100 — High-voltage AC circuit breakers — Part 100
- GB1984 — AC High Voltage Circuit Breaker
- GB/T11022 — Common technical requirements for high-voltage switchgear
- DL/T402 — High-voltage AC circuit breaker
- JB/T3855 — High-voltage AC vacuum circuit breaker
Service Conditions- Ambient temperature: -25°C to +40°C
- Altitude: ≤ 1000 m
- Relative humidity: daily average ≤ 95%; monthly average ≤ 90%
- Daily average vapor pressure ≤ 2.2×10-3 MPa; monthly average ≤ 1.8×10-3 MPa
- Seismic intensity ≤ 8
- Location free from dripping water, flammable/explosive atmosphere, corrosive gases and severe vibration
Technical parameter (summary)- Rated frequency: 50/60 Hz
- Rated voltage: 12 kV
- Rated power-frequency withstand voltage (phase-phase / phase-earth): 42 kV
- Rated insulation fracture withstand voltage: 48 kV
- Rated lightning impulse withstand voltage (phase-phase / phase-earth): 75 kV; isolation: 85 kV
- Rated current options: 630 A, 1250 A
- Rated short-circuit breaking current (r.m.s): 20, 25, 31.5 kA
- Short-time withstand current/time: 20/4, 25/4, 31.5/4 kA/s
- Rated peak withstand current / making current: 50, 63, 80 kA
- Rated breaking current for capacitor bank: 400(630)/400 A
- Capacitor bank making current: 2.5 kA (freq. ≤ 1000 Hz)
- Mechanical life: 10,000 operations
- Main circuit resistance per phase: ≤ 80 mΩ (one variant), ≤ 70 mΩ (other)
- Contact clearance (open): 9 ± 1 mm
- Contact travel: 5.5 ± 1 mm
- Contact closing bounce time: ≤ 2 ms
- Three-phase asynchronous closing/opening: ≤ 2 ms
- Average opening speed: 0.9 ~ 1.3 m/s
- Average closing speed: 0.4 ~ 0.8 m/s
- Rated contact pressure: 2400 ± 200 N (20–25 kA); 3100 ± 200 N (31.5 kA)
- Opening time (at rated voltage): ≤ 45 ms
- Closing time (at rated voltage): ≤ 70 ms
- Rated operating sequence: O-0.3s-CO-180s-CO
Technical characteristics- Integrated operating mechanism with multi-prevention interlocks and modular sealed poles assembled on a common mounting frame
- Integrated indicators for primary circuit and operating panel for clear status readout and interlocked operation
- Compact footprint compared with similar air-insulated equipment; cabinet width can be as small as 500 mm
- Low maintenance: maintenance-free vacuum arc-extinguishing chambers with long service life
- Visual and dimensional consistency across VTD9 breakers, FTD9 load switches and GTD isolating switches to simplify cabinet expansion
Basic structure and typical components- Upper terminal
- Wall-through pole
- Isolation switch
- Operating mechanism (box)
- Cable terminal
- Earthing switch
- Installation rack
- Door interlocking boards
- Earthing switch operation hole
- Earthing switch ON/OFF indication
- Energy storage status indication
- Counter
- Circuit breaker open/close status indication
- Energy storage handle
- Opening and closing buttons
- Isolation switch ON/OFF indication
Typical outline dimensions (summary)- Rated current (A): 630 / 1250
- Rated short-circuit breaking current (kA): 20, 25, 31.5
- Inter-phase distance (mm): 210
Characteristics / specifications- Model: VTD9-12D
- Rated frequency: 50/60 Hz
- Rated voltage: 12 kV
- Rated current options: 630 A, 1250 A
- Breaking current options (r.m.s): 20, 25, 31.5 kA
- Short-time withstand current/time: 20/4, 25/4, 31.5/4 kA/s
- Peak withstand / making currents: 50, 63, 80 kA
- Mechanical life: 10,000 operations
- Contact clearance open: 9 ± 1 mm
- Opening time (rated voltage): ≤ 45 ms; Closing time (rated voltage): ≤ 70 ms