Application ScopeSuitable for building automation and intelligent control systems, burglar alarm and access control systems, smart home installations, mechanical instruments and electronic devices requiring shielded anti-interference signal cables. Rated for AC voltage U0/U 300/300V or below.
Notes- Material: Conductor made of high-purity oxygen-free copper, stranded; insulation and sheath made of environmentally friendly PVC; shielding consists of aluminum foil combined with high-density tin-plated copper braided mesh.
- Standards: JB/T8734.5-2016. Voltage rating: U0/U 300/300V.
Operating Characteristics- Long-term operating temperature: ≤ 70℃
- Cable laying ambient temperature: ≥ 0℃
- Bending radius (flexible cable): D < 25 mm → ≥ 4D; D ≥ 25 mm → ≥ 6D
- Structure: Conductor + Insulation (two-layer structure)
Parameter TableSpecification (mm²) | Conductor Structure (n/mm) | Insulation Thickness (mm) | Sheath thickness (mm) | Finished product outer diameter (mm) | Conductor Resistance at 20℃ (Max, Ω/km) | Insulation Resistance at 70℃ (Min, MΩ·km) | Current - Carrying Capacity Reference Value A
2*0.12 | 7/0.15 | 0.4 | 0.6 | 3.8 | 158.0 | 0.016 | 1.0
2*0.2 | 12/0.15 | 0.4 | 0.6 | 4.3 | 92.3 | 0.013 | 2.0
2*0.3 | 16/0.15 | 0.5 | 0.6 | 5.1 | 69.2 | 0.014 | 3.0
2*0.5 | 16/0.20 | 0.5 | 0.6 | 5.8 | 39.0 | 0.013 | 5.0
2*0.75 | 24/0.20 | 0.5 | 0.6 | 6.2 | 26.0 | 0.012 | 7.0
2*1.0 | 32/0.20 | 0.6 | 0.7 | 7.2 | 19.5 | 0.010 | 11.0
2*1.5 | 48/0.20 | 0.7 | 0.8 | 7.9 | 13.3 | 0.009 | 17.0
2*2.5 | 49/0.25 | 0.8 | 1.0 | 9.7 | 7.98 | 0.009 | 26.0
2*4.0 | 81/0.25 | 0.8 | 1.2 | 11.3 | 4.95 | 0.007 | 35.0
3*0.12 | 7/0.15 | 0.4 | 0.6 | 4.3 | 158.0 | 0.016 | 1.0
DownloadDatasheet available (PDF).
Technical specifications- Series: RVVP (shielded PVC insulated flexible signal cable).
- Voltage rating: U0/U 300/300V.
- Standard: JB/T8734.5-2016.
- Conductor: High-purity oxygen-free copper, stranded (see conductor constructions in parameter table).
- Insulation / Sheath: Environmentally friendly PVC for insulation and outer sheath.
- Shielding: Aluminum foil combined with high-density tin-plated copper braided mesh for EMI/RFI protection.
- Operating temperature (long-term): ≤ 70℃; laying ambient temperature ≥ 0℃.
- Bending radius (flexible cable): D < 25 mm → ≥ 4D; D ≥ 25 mm → ≥ 6D.
- Typical electrical/mechanical data: conductor resistance, insulation resistance and current-carrying reference values given in the parameter table for sizes from 2×0.12 mm² up to 2×4.0 mm² (and 3×0.12 mm²).
- Structure note: conductor + insulation (two-layer structure).