The device is primarily built to monitor thermotechnical processes accurately and switch the systems to a safe operating status in the event of malfunctions. As a result, risks to people, the environment, production facilities, and production goods can be identified and averted at an early stage.
Internal and external unlocking
Wide voltage supply range
general technical data
Linearization - 12 linearizations can be set
Pt100 DIN IEC 60751:2008 - -200 to +850 °C
Pt1000 DIN IEC 60751:2008 - -200 to +850 °C
Error tolerance time - ≤ 5 s time taken into account for all diagnostic tests
Input filter - Digital filter, 2nd order, filter constant can be set from 0 to 100 s