video corpo

Electromechanical relay module GRV-OMRIS-8
DCACwith LED indicator

Electromechanical relay module - GRV-OMRIS-8 - Opto 22 - DC / AC / with LED indicator
Electromechanical relay module - GRV-OMRIS-8 - Opto 22 - DC / AC / with LED indicator
Electromechanical relay module - GRV-OMRIS-8 - Opto 22 - DC / AC / with LED indicator - image - 2
Electromechanical relay module - GRV-OMRIS-8 - Opto 22 - DC / AC / with LED indicator - image - 3
Electromechanical relay module - GRV-OMRIS-8 - Opto 22 - DC / AC / with LED indicator - image - 4
Electromechanical relay module - GRV-OMRIS-8 - Opto 22 - DC / AC / with LED indicator - image - 5
Electromechanical relay module - GRV-OMRIS-8 - Opto 22 - DC / AC / with LED indicator - image - 6
Add to favorites
Compare this product

Characteristics

Type
DC, AC, electromechanical
Other characteristics
with LED indicator, 8-channel
Protection level
isolated
Load current

Max.: 5 A

Min.: 0 A

Load voltage

Max.: 250 V

Min.: 0 V

Description

Overview
  • Mechanical relay output module for groov EPIC providing 8 independent, isolated electromechanical Form C (changeover) channels.
  • Each channel can be wired normally open or normally closed to switch AC or DC loads.
  • Module cover includes an LED status indicator and a touch-sensitive pad that displays module information and wiring diagrams on the groov EPIC processor.
  • Channel-to-channel isolation and very low contact leakage when open make the module suitable for driving electronic coil contactors and mixed-load applications.
  • Mounts on a groov EPIC chassis with a GRV-EPIC-PR1 processor and integrates with other groov I/O modules (analog, discrete, serial).
  • Factory tested twice before shipment; warranty: 30 months.


Technical specifications
  • Number of Channels: 8
  • Line Voltage Range (nominal): 0–250 VAC or 5–30 VDC
  • Current Rating: 5 A per channel
  • Surge Current: 6 A peak for 1 second
  • Recommended Fuse / Circuit Breaker: 5 A at 250 VAC / > 30 VDC per channel (fusing not provided)
  • Leakage Current: < 2 µA @ 250 VAC
  • Contact Resistance: ≤ 100 mOhms
  • Turn-on Time: 8 ms
  • Turn-off Time: 4 ms
  • Operating Life (to specification): Min. 30,000 cycles at max. ratings
  • Mechanical Life: Min. 10,000,000 cycles
  • Transient Clamp Holding Voltage: 440 V
  • Transient Clamping Voltage (max.): 720 V
  • Isolation (coil-to-contact): 4000 VAC rms, 1 min., 10 mA detect/channel
  • Isolation (channel-to-channel): 300 VAC operating, 1500 V rms max.
  • Chassis Power Consumption: 1.4 W
  • Minimum groov EPIC Firmware Version: 1.0.0
  • Minimum PAC Project Version: 10.0000
  • Minimum Library Package for CODESYS Version: 1.0.0.0
  • Wire Size: 28–14 AWG
  • Wire Strip Length: 0.315–0.354 inches (8–9 mm)
  • Torque, connector screw: 2.5 in-lb (0.28 N·m)
  • Torque, hold-down screw: 3.5 in-lb (0.4 N·m)
  • Temperature (operating): -20 °C to +70 °C
  • Temperature (storage): -40 °C to +85 °C
  • Shock (misoperation): 5 G
  • Shock (survival): 100 G
  • Relative Humidity (non-condensing): 5–95%
  • Agency Approvals: UL/cUL (Class 1, Div 2); CE: ATEX (Category 3, Zone 2) and RoHS; DFARS; CB Scheme; UKCA
  • Warranty: 30 months

Catalogs

No catalogs are available for this product.

See all of Opto 22‘s catalogs

Other Opto 22 products

I/O