video corpo

Digital output module GRV-OACI-12
12-O12 Digital outputsEPIC

Digital output module - GRV-OACI-12 - Opto 22 - 12-O / 12 Digital outputs / EPIC
Digital output module - GRV-OACI-12 - Opto 22 - 12-O / 12 Digital outputs / EPIC
Digital output module - GRV-OACI-12 - Opto 22 - 12-O / 12 Digital outputs / EPIC - image - 2
Digital output module - GRV-OACI-12 - Opto 22 - 12-O / 12 Digital outputs / EPIC - image - 3
Digital output module - GRV-OACI-12 - Opto 22 - 12-O / 12 Digital outputs / EPIC - image - 4
Digital output module - GRV-OACI-12 - Opto 22 - 12-O / 12 Digital outputs / EPIC - image - 5
Digital output module - GRV-OACI-12 - Opto 22 - 12-O / 12 Digital outputs / EPIC - image - 6
Add to favorites
Compare this product

Characteristics

Signal type
digital
Number of inputs/outputs
12-O, 12 Digital outputs
Bus standard
EPIC
Type
distributed
Applications
automation, for hazardous locations, for control cabinets, for motors
Other characteristics
insulated

Description

Overview
  • The GRV-OACI-12 is a groov EPIC digital AC discrete output module providing 12 independently managed AC outputs suitable for industrial control and monitoring applications requiring isolated AC switching.


Features
  • 12 independent AC discrete output channels
  • Channel-to-channel isolation
  • LED status indicator and touch-sensitive pad on the module cover
  • Zero-voltage turn-on and zero-current turn-off to minimize switching transients
  • On/off state reporting
  • Output pulsing (TPO)
  • On/off totalization
  • Open-circuit indication
  • Watchdog timeout support


Technical specifications
  • Model: GRV-OACI-12
  • Number of channels: 12
  • Line voltage: 12–250 VAC
  • Current rating (per channel): 0.5 A
  • Recommended maximum fuse (fast) or circuit breaker: 2 A 250 VAC per channel, 6 A 250 VAC common
  • Minimum load current: 20 mA
  • Output voltage drop: 1 V
  • Off-state leakage at nominal voltage (60 Hz): 1.25 mA @240 VAC; 0.7 mA @120 VAC
  • Peak blocking voltage: 500 V
  • Operating frequency: 40 to 60 Hz, 400 Hz
  • Turn-on time: ≤ 1/2 cycle (zero crossing)
  • Turn-off time: ≤ 1/2 cycle (zero crossing)
  • TPO period: 0.1 s to 429496.7296 s, resolution 0.001 s
  • Isolation (field-to-logic): 300 V working, 1500 V transient (1 minute)
  • Isolation (channel-to-channel): 300 V working
  • Chassis power consumption: 1.3 W
  • Minimum groov EPIC firmware version: 1.0.0
  • Minimum PAC Project version: 10.0000
  • Minimum Library Package for CODESYS version: 1.0.0.0
  • Wire size: 28–14 AWG
  • Wire strip length: 0.315–0.354 inches (8–9 mm)
  • Torque, connector screw: 2.5 in-lb (0.28 N·m)
  • Torque, hold-down screw: 3.5 in-lb (0.4 N·m)
  • Operating temperature: -20 °C to +70 °C
  • Storage temperature: -40 °C to +85 °C
  • Relative humidity (non-condensing): 5–95%
  • MTBF (minimum, 25 °C): 1.2 Mhrs
  • Agency approvals: UL/cUL (Class 1, Div 2); CE: ATEX (Category 3, Zone 2) and RoHS; DFARS; CB Scheme; UKCA
  • Warranty: Lifetime


Applications
  • Isolated AC switching in distributed I/O systems
  • Pump, heater and motor control
  • Process control and factory automation
  • Use in hazardous locations per listed approvals