Short description- Energy savings due to integrated electronic power adjustment
- Optional interfaces for bus communication using plug-in IF-Modules
- Simple operation due to tried-and-tested Green Button Technology and display
- Integrated full motor protection (PTC thermistor sensor) with trip electronics
- Meets user requirements thanks to performance and main dimensions in accordance with EN 733 (for end-suction pumps)
Product selection (excerpt)Number of results: [312]
Product description | MEI | IE | Pipe connection, suction side DNs | Pipe connection, discharge side DNd | Mechanical seal | Rated power P2 (kW) | Phase | Article number | GRD group
CronoBloc-BL-E32/95-1,5/2 | 0.4 | IE4 | DN 50 | DN 32 | AQ1EGG | 1.5 kW | 3 | 2222270 | 12
CronoBloc-BL-E32/95-1,5/2-R1 | 0.4 | IE4 | DN 50 | DN 32 | AQ1EGG | 1.5 kW | 3 | 2222272 | 12
CronoBloc-BL-E32/95-1,5/2-R1-S1 | 0.4 | IE4 | DN 50 | DN 32 | Q1Q1X4GG | 1.5 kW | 3 | 2222273 | 12
CronoBloc-BL-E32/95-1,5/2-S1 | 0.4 | IE4 | DN 50 | DN 32 | Q1Q1X4GG | 1.5 kW | 3 | 2222271 | 12
CronoBloc-BL-E32/105-2,2/2 | 0.4 | IE4 | DN 50 | DN 32 | AQ1EGG | 2.2 kW | 3 | 2222434 | 12
CronoBloc-BL-E32/105-2,2/2-R1 | 0.4 | IE4 | DN 50 | DN 32 | AQ1EGG | 2.2 kW | 3 | 2222436 | 12
... (additional variants available; table contains many more rows)
DesignElectronically controlled glanded single pump in close-coupled design with flange connection and automatic power adjustment.
ApplicationThe pumping of heating water (in accordance with VDI 2035), chilled water and water-glycol mixtures without abrasive substances in heating, chilled water and cooling systems.
Equipment / FunctionOperating modes- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- PID-Control
- Constant speed (n = constant)
Manual operation levelManual functions- Differential pressure setpoint setting
- Setting the speed (manual control mode)
- Setting the operating mode
- Setting the pump ON/OFF
- Configuration of all operating parameters
- Fault acknowledgement
External control functions- 1x “Overriding Off” control input
- 1x “External pump alternation” control input (effective only in twin-head pump operation)
- 1x Analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for constant speed (DDC) and remote setpoint adjustment
- 1x Analogue input 0–10 V, 2–10 V, 0–20 mA, 4–20 mA for actual value signal from pressure sensor
Signal and display functions- Collective fault signal SSM
- Collective run signal SBM
Data exchange- Infrared interface for wireless data exchange with IR‑Stick
- Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation
- Interface to dual-pump communication
Safety functions- Full motor protection with integrated trip electronics
- Access disable
Dual-pump management (2 x single pump; Y-piece application only)- Main/standby operation (automatic fault-actuated switchover)
- Pump alternation main/standby operation after 24 hours
- Parallel operation
- Parallel operation (efficiency-optimised peak load activation and deactivation)
Type key (example)Example: BL-E 80/145-11/2-xx where BL-E = Close-coupled end suction pump with electronic control; 80 = nominal diameter DN of the pipe connection (discharge port); 145 = nominal impeller diameter in mm; 11 = rated power of motor P2 in kW; 2 = number of poles; -xx = version (e.g. R1 = version without differential pressure sensor).
Scope of delivery- Pump
- Installation and operating instructions
Options- Variant …-R1 without differential pressure sensor
- …-L1 variant with bronze impeller (at additional charge)
- …-L4 variant with stainless steel impeller (at additional charge)
Accessories- Supporting blocks for installation on a base
- IR‑Stick
- IF module PLR for connecting to PLR/interface converter
- IF module LON for connection to the LONWORKS network
- IF module BACnet
- IF module Modbus
- IF module CAN
- Control system VR-HVAC / CCe-HVAC / SCe-HVAC
- Differential pressure sensor (DDG)
Caractéristiques / spécifications techniques- Permissible temperature range: -20 °C to +140 °C
- Minimum efficiency index (MEI) ≥ 0.4
- Mechanical seal suitable for pumping water up to Tmax = +140 °C. For water-glycol mixtures up to T ≤ +40 °C a glycol admixture of 20% to 40% by volume is permissible. For glycol > 40% (up to 50%) and higher temperatures or other fluids, an alternative mechanical seal is required; S1 variant recommended when using water-glycol mixtures.
- Mains connection options: 3~440 V -5% +10% 50/60 Hz; 3~400 V ±10% 50/60 Hz; 3~380 V -5% +10% 50/60 Hz
- Compliance with electromagnetic compatibility without additional measures: Emission for residential environment and immunity for industrial environments according to EN 61800-3:2018
- Protection rating IP55
- Nominal diameter DN 32 to DN 150 (discharge)
- Max. operating pressure: 16 bar up to +120 °C; 13 bar up to +140 °C
- Materials: Pump housing and lantern EN-GJL-250; Impeller standard EN-GJL-200 (options: Bronze CuSn 10 or Stainless steel 1.4408); Shaft 1.4122; Mechanical seal AQEGG (other seals on request)
- Construction: Single-stage low-pressure centrifugal pump in close-coupled design, axial suction port, radial discharge port, mechanical seal, flange connection with pressure measuring connection R 1/8, lantern, pump housing with feet, coupling, drive with integrated electronic speed control