Features:
· Type 1 Class I surge protector.
· Status indication.
· Uc: 385V / 275V.
· Iimp: 25kA / 50kA.
· Maximum discharge current (8/20us): 100kA.
· Pole number: 1+1NPE.
· BR-25GR 1+1NPE surge arrester is suitable for TT and TN-S system.
Application:
· Protect against direct hit of lightning strokes of medium intensities.
· Suitable for protection of electrical installations against transient overvoltage caused by direct and indirect lightning strikes or switching processes.
· Mainly to main distribution boards, for protection against impact of direct or indirect lightning strikes in wide range of applications – houses, office or industrial buildings, resp. to sub-distribution boards in large buildings.
Advantage:
· High discharge capacity.
· Low let-through voltage.
Installation:
· Type 1 or Type 1+2 SPD (Iimp ≥ 12.5 kA) compulsory at the installation source (main distribution board in secondary buildings).
· Installations more than 10 m high (apartment buildings, office buildings, hotels, etc.): type 2 SPD recommended for protecting private areas and floor distributors (communal areas) in addition to a type 1 or type 1+2 SPDs.