• Products
  • Catalogs
  • News & Trends
  • Exhibitions

Shut-off valve OPD
overfill preventionfuelpetroleum

Shut-off valve - OPD - Neftgen - overfill prevention / fuel / petroleum
Shut-off valve - OPD - Neftgen - overfill prevention / fuel / petroleum
Shut-off valve - OPD - Neftgen - overfill prevention / fuel / petroleum - image - 2
Add to favorites
Compare this product

Characteristics

Function
overfill prevention
Media
for diesel, gasoline, fuel, petroleum
Body
female-female
Applications
for liquids, for tanks
Fluid specification
for flammable fluids
Associated function
for filling applications
Other characteristics
ANSI, automatic, total isolation
DN

Max.: 100 mm
(3.937 in)

Min.: 50 mm
(1.969 in)

Pressure

Max.: 8 bar
(116 psi)

Min.: 0 bar
(0 psi)

Temperature

Max.: 60 °C
(140 °F)

Min.: -25 °C
(-13 °F)

Flow rate

Max.: 1,400 l/min
(369.84 us gal/min)

Min.: 0 l/min
(0 us gal/min)

Description

Product Overview
Overfill Prevention Valves (OPV/OPD) designed for automatic total shut-off during filling of underground and aboveground atmospheric fuel tanks. Suitable for diesel, gasoline and other petroleum liquids. All-metal, maintenance-free construction optimized for manhole installation and compatible with gravity or pumped filling systems.

Key Features
  • Automatic total shut-off overfill protection
  • Compatible with diesel, gasoline and petroleum liquids
  • For underground and aboveground tanks
  • All-metal, maintenance-free construction
  • Compatible with gravity and pumped filling
  • Easy manhole installation
  • Individually tested and serialized


Advantages
  • Maintenance-free operation
  • High reliability in fuel environments
  • Extended service life
  • Guaranteed closure safety to prevent spills


Technical Characteristics
  • Sizes: DN50, DN80, DN100
  • Connections: BSPP F/F
  • Operating temperature: -25°C to +60°C
  • Flow capacity: up to 84 m³/h
  • Maximum working pressure: up to 8 bar


Standards & Compliance
  • ATEX 2014/34/EU
  • EN 13616-1:2016
  • KIWA BRL-K636/03
  • ANSI / UL / ULC 2583


Technical Documents
  • OPD Datasheet
  • Declaration of Performance (DoP) DN100
  • Declaration of Performance (DoP) DN80
  • Declaration of Performance (DoP) DN50
  • Installation Manual
  • Comparative Table


Specifications / Technical Specifications
  • Product type: Overfill Prevention Valve (OPV / OPD)
  • Applications: diesel, gasoline and petroleum liquids; suitable for underground and aboveground atmospheric tanks
  • Construction: all-metal, maintenance-free
  • Installation: manhole-mounted; compatible with gravity and pumped filling
  • Testing: individually tested and serialized
  • Sizes available: DN50, DN80, DN100
  • Connections: BSPP F/F
  • Operating temperature range: -25°C to +60°C
  • Flow rate: up to 84 m³/h
  • Maximum working pressure: up to 8 bar
  • Standards: ATEX 2014/34/EU; EN 13616-1:2016; KIWA BRL-K636/03; ANSI/UL/ULC 2583
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.