The InnovairFlex DNR Intelligent Photoelectric Duct Smoke Detector features a pivoting housing that fits both square and rectangular footprints, capable of mounting to a round or rectangular duct. These units sense smoke in the most challenging conditions, operating in airflow speeds of 0.5 to 20 meters per second, temperatures of -20°C to 70°C and a relative humidity range of 0 to 95 percent, non-condensing. An improved cover design isolates the sensor head from the LowFlow feature for simple maintenance. A Cover Tamper feature provides a fault signal if the sensor cover is removed or improperly installed. The InnovairFlex housing has a 20mm conduit knockout and ample space for wiring. The InnovairFlex Duct Smoke Detector can be customized to meet local requirements and specifications without additional wiring. The product line utilises a new sampling tube range, but remains compatible with all previous Innovair models, including remote test accessories.
Features
Utilises standard plug-in conventional photo-electronic smoke detector (supplied separately)
Integrated low-flow technology
Air velocity rating from 0.5 m/s to 20 m/s
Versatile mounting options: square or rectangular configuration
Broad ranges for operating temperature (-20 °C to 70 °C) and humidity (0% to 95% non-condensing)
Sampling tube installs from front or rear of the detector
Transparent cover for convenient visual inspection
Cover tamper signal
Large wiring space with 3 x 20 mm conduit knockouts
Remote test ability, with external power and RTS451KEY
Powered from the analogue addressable loop
UL 268A listed for duct detection applications