Product overviewSP-XL is a floor-standing low-voltage power distribution cabinet for 3-phase 3-/4-/5-wire systems up to 400 V AC. Designed for power and lighting distribution in industrial and infrastructure applications, it is suitable for power plants, rail, aerospace, oil & gas, metallurgy, textile, construction and steel works.
Compliance with standards- GB/T7251.12-2013
- IEC 61439-1
- GB 10233
- GB17625.1-2003
- GB 16838-2005
- GB 4208 (IP code)
- GB50171-2002
Technical characteristics and advantages- Surface protection: automatic high-voltage electrostatic powder coating; typical film thickness 60–80 μm; adhesion and salt-spray resistance up to 168 h.
- Cabinet design: modular assembly concept; C-profile frame; door with inclined edge and lock options; space allocated for wiring and components; available assembly or welded types.
- Electrical connections: main and branch busbars in Copper T2 with surface treatment; CNC processing and cold-press terminals for accurate, reliable contacts; heat-shrink insulation on non-conductive surfaces.
- Verification: design verification according to IEC 61439-1 and 7+5 comprehensive test items.
7+5 comprehensive test standards (structure inspection vs performance inspection)Structure inspection — Performance inspection
1 — Strength of materials and parts — 1 — Dielectric property
2 — Protection class of complete equipment — 2 — Verification of temperature rise
3 — Electrical clearance and creepage distance — 3 — Short-circuit withstand strength
4 — Integrity of protection against electric shock and protective circuit — 4 — Electromagnetic compatibility
5 — Combination of switching devices and components — 5 — Mechanical operation
6 — Internal circuit and connection — (—)
7 — External terminal — (—)
Environmental conditions for use- Installation altitude: standard up to 2000 m (derating required above 2000 m); not to exceed 4500 m without consultation.
- Intended for indoor locations without dust, corrosive gases or direct rain (outdoor variants per IP rating).
- Ambient temperature: −25 °C to +40 °C (24 h average ≤ +35 °C).
- No significant vibration or shock; installation tilt ≤ 5°.
- For special site requirements consult manufacturer.
Main circuit scheme (symbol notes)Common device symbols listed: fuse switches (QSA, HR5, HR6), isolating switches (QA, QP), fuse types (RTO, NT00), circuit breakers (M1, DZ15, DZ20, DZ47), contactors (CJ20, CJX series), thermal relays (JR20 series), current transformers (BH-0.66, LMZJ1-0.5, LMK1-0.66). Specific component models can be specified at order.
Ordering instructionPlease specify on order:
- Product model (SP-XL) and required cabinet type (assembly/welded)
- Main circuit system diagram and layout
- Auxiliary circuit schematic
- List of components and main bus specification
- Cabinet color (standard RAL7035) and dimensions
- Any special requirements or site conditions
Technical specifications- Model: SP-XL
- Rated current: ≤1250 A
- Rated insulation voltage Ui: 800 V AC
- Rated operating voltage: 400 V AC
- Rated impulse withstand voltage: 8 kV
- Frequency: 50 Hz
- Rated short-time withstand current Icw (1 s): ≤30 kA
- Degree of protection: up to IP65
- Operation: indoor / outdoor (depending on configuration)
- Maximum altitude: 2000 m (derating above)
- Ambient temperature (average 24 h): ≤ +35 °C
- Pollution degree: 3
- Box material: cold-rolled steel, stainless steel or Al-Zn plate
- Coating: electrostatic epoxy powder
- Color: RAL7035 standard or custom
- Internal insulation: high-temperature and fire-resistant material
- Cabinet structure: assembly type or welded type