1 Product OverviewSP-JP intelligent low-voltage integrated distribution cabinet is a next-generation outdoor low-voltage distribution cabinet designed for 0.4 kV distribution systems. It integrates metering, measurement, control, protection, power distribution, reactive power compensation, harmonic control and three-phase imbalance adjustment. The cabinet is suitable for transformer secondary installations up to 500 kVA, urban and rural distribution networks, industrial sites, street lighting and residential communities.
2 Compliance with Standards- GB/T 7251.1-2013 (IEC 61439-1:2011, IDT) — Low-voltage switchgear and controlgear assemblies — Part 1: General rules
- GB/T 7251.8-2005 — General technology requirements for intelligent assemblies
- GB/T 7251.12-2013 (IEC 61439-2:2011, IDT) — Power switchgear and controlgear assemblies
- GB/T 10233-2016 — Basic testing method
- GB/T 15576-2008 — Low-voltage reactive power compensation assemblies
- DL/T 375 — General technical conditions for outdoor distribution box
- DL/T 645 — Multifunction watt-hour meter communication protocol
- DL/T 842 — Application specification for low-voltage shunt capacitor installation
- DL/T 1441-2015 — Technical conditions for intelligent low-voltage distribution box
- DL/T 1442 — Technical conditions for intelligent distribution transformer terminal
3 Product ApplicationDesigned as an integrated transformer distribution cabinet, SP-JP performs power distribution, metering and protection functions (overload, short circuit, leakage, over/under voltage, phase loss), automatic reclosing, lightning protection and capacitor-based reactive power compensation. Typical uses: rural grid reconstruction, urban distribution, industrial and mining sites, street lighting and residential areas.
4 Technical Characteristics and Advantages- Robust outdoor enclosure meeting IP44 (door design can reach IP54); anti-dust, rainproof and anti-electromagnetic interference features.
- Integrated door-open lighting with status upload to the terminal for event records.
- Intelligent monitoring collects voltage, current and cable temperature, supports remote measurement/signaling and fault diagnosis (reports overvoltage, undervoltage, overcurrent, phase loss to master station).
- Emergency power interface for generator or supply vehicle to maintain critical loads during maintenance or faults.
- Automatic three-phase imbalance adjustment to reduce transformer stress, equipment impact and line losses.
5 Operating and Environment Conditions- Altitude ≤ 2,000 m (above: capacity derating).
- Outdoor use without excessive dust or corrosive gas; pollution degree 3.
- Ambient temperature: -25 °C to +40 °C (24 h average ≤ +35 °C).
- Relative humidity: ≤ 50% at +40 °C; higher humidity allowed at lower temperatures (e.g. 90% at +20 °C), consider condensation.
- Installation tilt: vertical plane inclination ≤ 5°.
- Conditions outside these limits must be specified as special conditions when ordering.
6 Main Technical ParametersRated short-circuit withstand current Icw | Unit | Value
Rated short-circuit withstand current Icw | KA | 30KA/1S
Rated operating current | A | ≤800A
Rated insulation voltage U1 | V | AC690V
Rated operating voltage Ue | V | AC400V
Rated compensation capacity | | 10~130 Kvar
Compensation method | | Separate compensation + mutual compensation
Rated impulse withstand voltage Uimp | KV | 8KV
Overvoltage grade | | IV
Rated frequency | Hz | 50Hz
Enclosure protection degree | | IP44
Environmental temperature for use | ℃ | -25 ℃ ~ 45 ℃
7 Structural Characteristics- Integrated insulated busbar system reduces temperature rise and improves stability.
- Cabinet can be equipped by transformer capacity with intelligent distribution terminal, reactive power controller, measuring current transformers, isolating fuse switch, high-breaking auto-reclosing leakage protection breaker, intelligent capacitor banks, lightning protection and other components; functional data collected by the terminal and transmitted via GPRS or optical fiber.
- Fine reactive power compensation using small-capacity capacitors to avoid over-compensation; compensation units include protections against overcurrent, overvoltage, undervoltage, phase loss and switching oscillation locking.
- Main frame made of ≥2 mm anti-glare stainless steel with partial welding or patented double-layer heat insulation; modular hole columns, flanged waterproof diversion trench and top cover; louvers and bridge-type ventilation for heat dissipation; door sealed with PU foam strip (can reach IP54).
- Compartmentalized layout: metering unit, incoming line unit, feeder unit, reactive compensation unit, intelligent control unit and auxiliary unit separated by galvanized steel plates.
- Flexible incoming/outgoing line modes: side incoming; side/bottom outgoing; stainless-steel waterproof elbows with rubber ring to protect cables.
8 Typical Application Scheme and DiagramsTypical application, installation and component layout diagrams are available for 400 kVA and 200 kVA variants. Example component list rows: QS1 | Fuse-type isolating switch | 630A(800A); TA1/TA2 | Current transformers | class ≥0.5S; FB | Lightning arrester; SPD | Surge protective device T1; C1/C2 | Intelligent capacitor banks (mutual/separate compensation); BK | Intelligent distribution terminal; 3QF/4QF/5QF | Circuit breakers with residual current protection (ratings per transformer capacity). Detailed schematics and BOM to be provided with project-specific configuration.