Product descriptionThis series of cable junction cabinets is designed for outdoor distribution networks with AC 50 Hz and a rated voltage of 12 kV. They accept cable inlet and outlet lines and are used in industrial parks, residential areas, commercial centres, mining sites, airports, railways, ports and power stations. Particularly suitable for urban power grid upgrade projects.
Key features- Fully insulated, fully sealed and maintenance-free enclosure providing reliable personnel protection.
- Reduces complexity of urban cable networks and lowers infrastructure investment.
- Outdoor design: dustproof, moisture-proof, flood-resistant and corrosion-resistant; configurable for 2 to 8 access lines to meet various connection requirements.
- Compact footprint and low height for easy site integration; simple installation with optional live display, short-circuit indicator and lightning arrester.
- 200 A load-break cable head for plug-in/plug-out under load with isolating switch function; optional short-circuit fault indicator for fast fault location.
- Accepts combinations of load switches, circuit breakers and cable joints to improve operation flexibility and reduce outage time.
Normal use environmental conditions- Altitude: ≤ 1000 m.
- Ambient temperature: -30°C to 40°C.
- Relative humidity: ≤ 95%.
- Ambient air not heavily polluted by combustible gas; smoke, dust and corrosive gases permitted within GB/T5582 pollution level II.
- No frequent severe vibration.
Main technical parametersRated voltage (kV): 12
Rated frequency (Hz): 50
Rated current (A): 630
1 min power frequency withstand voltage (kV): 42
Lightning impulse withstand voltage (kV): 75
Protection level: IP54
Dimensions (L×W×H) (mm): 650×1150×880 ~ 1300×1500×1200
Remark: Can be equipped with load switches, circuit breakers, fuses and other accessories; see accessory specifications for equipment parameters.
Order notice- a. Specify model variant: European or American.
- b. Provide wiring scheme or number of branches; specify arrester type.
- c. Choose domestic or imported cable accessories.
- d. Indicate if live indicator and short-circuit fault indicator are required.
- e. Provide cable cross-section sizes for the main circuit and branch circuits.
- f. Specify box material (e.g., stainless steel or galvanized steel plate).
Characteristics / Technical specifications- Series: YB series
- Rated voltage: 12 kV
- Rated frequency: 50 Hz
- Rated current: 630 A
- 1 min power frequency withstand voltage: 42 kV
- Lightning impulse withstand voltage: 75 kV
- Protection level: IP54
- Dimensions (mm): from 650×1150×880 to 1300×1500×1200
- Outdoor SMC (fiberglass) enclosure – dustproof, moisture-proof, flood-resistant and corrosion-resistant
- Supports 2–8 branch access lines; supports load switches, circuit breakers, fuses, short-circuit indicators and lightning arresters