Product descriptionYBM, YBP (ZBW) series box-type prefabricated combined transformer substations integrate high-voltage switchgear, transformer(s) and low-voltage switchgear into a compact, complete power distribution unit for receiving and distributing electricity in urban high-rise buildings, residential communities, parks, industrial and high‑tech zones, small and medium factories, mines, oilfields and temporary construction sites. The unit has a three-compartment layout (high-voltage room, transformer room, low-voltage room), small footprint and is designed to reduce civil works compared with conventional substations. It is suitable for ring network distribution, dual-source supply or terminal (radial) systems and complies with GB 17467-2010 SD320.
Normal use environmental conditions- Altitude: up to 1000 m
- Ambient temperature: -25°C to +40°C (24 h average ≤ +35°C)
- Wind speed: ≤ 35 m/s
- Air relative humidity and site: normal installation conditions; no conductive dust or corrosive/flammable/explosive substances harmful to metals or insulation
- Seismic and installation: horizontal acceleration within design limits; no severe vibration; installation slope ≤ 3°
Main technical parametersRated high-voltage: 7.2/12 kV. Transformer secondary voltages: 6/0.410/0.4 kV. Rated transformer capacity: selectable, examples 50–1250 kVA per unit; combined arrangement up to 2×1250 kVA. Typical HV rated current 200–630 A; LV up to 100–3000 A depending on configuration. Short-time withstand, peak and making currents depend on configuration (examples: 20*(2) kA, 12.5*(4) kA, 31.5/63 kA). Power-frequency and lightning impulse withstand values specified per equipment. Noise: oil-immersed <55 dB; dry type <65 dB. Protection class: shell typically IP54. Dimensions vary with selected switchgear and transformer; example YBM29 1250 kVA L 5000 B 3000 H 2980.
Structural featuresThe unit is divided into three functional compartments: high-voltage room, transformer room and low-voltage room. HV and LV rooms are fully functional; HV side can be arranged for ring network, terminal or dual supply and fitted with HV metering components. Transformer options include low-loss oil-immersed types (S9, S11, SCB10, SCB13) and dry-type transformers. The transformer room is equipped with forced‑air cooling and lighting; a temperature controller can automatically regulate transformer temperature. The top cover is double-layer thermal insulation with ventilation eaves for convection. The base uses a sectional steel frame. Shell materials and finishes are selectable (non‑metallic, ordinary steel, stainless steel, aluminum alloy, color steel composite) with outdoor anti‑corrosion, waterproofing and dust protection. Cable in/out wiring is standard; other wiring methods available on request.
Plane layout and dimensionsRefer to the plane layout diagram on the product page. Typical dimensions (examples): YBM29 100–250 kVA L 3000 B 2000 H 2520 A 3320 C 2320; YBM29 315–630 kVA L 4000 B 2600 H 2560 A 4320 C 2920; YBM29 800–1000 kVA L 4600 B 2600 H 2560 A 4920 C 2920; YBM29 1250 kVA L 5000 B 3000 H 2980 A 5320 C 3320. YBP29 dimensions depend on the low‑voltage outlet arrangement.
Characteristics / technical specifications- Series / model family: YBM, YBP
- Standards: GB 17467-2010 SD320 (box-type substations)
- Rated HV voltage (Ue): 7.2 / 12 kV
- Transformer secondary voltages: 6 / 0.410 / 0.4 kV
- Rated capacity (Se): selectable up to 1250 kVA per unit; combined up to 2×1250 kVA
- Rated currents and short-circuit characteristics: depend on configuration (examples in table)
- Power-frequency and lightning withstand values: specified per equipment
- Noise level: oil-immersed <55 dB; dry type <65 dB
- Protection class: typically IP54
- Cooling & ventilation: natural and forced ventilation; transformer room with forced‑air cooling and automatic temperature control
- Structure and materials: three-compartment layout; selectable shell materials and surface treatments