Three-phase switchgear XGN2-12
ACmedium-voltagevacuum

Three-phase switchgear - XGN2-12 - SAIP ELECTRIC GROUP CO.,LTD - AC / medium-voltage / vacuum
Three-phase switchgear - XGN2-12 - SAIP ELECTRIC GROUP CO.,LTD - AC / medium-voltage / vacuum
Add to favorites
Compare this product

Characteristics

Electrical characteristics
medium-voltage, AC, three-phase
Configuration
metal-clad, vacuum
Applications
industrial, for power plants, power distribution
Other characteristics
draw-out, monobloc
Primary current

Min.: 630 A

Max.: 3,150 A

VAC

Min.: 3,600 V

Max.: 12,000 V

Description

Product description
XGN2-12 is a withdrawable, box-type, metal-enclosed indoor AC switchgear designed for reception and distribution of electrical energy in power plants, substations and industrial installations. It complies with national standard GB3906 and IEC298 and incorporates five-prevention mechanical interlocks for safe operation and maintenance.

Scope of application
This switchgear is intended for three-phase AC systems (single bus, double bus or single bus with bypass) at 50 Hz with rated voltages 3.6, 7.2 or 12 kV and rated current range 630–3150 A. Typical applications include power generation, distribution substations and heavy industrial or mining facilities.

Model meaning
XGN2-12 denotes a box-type (cabinet) design with withdrawable (withdrawable/insertable) units and configurations adapted to accommodate vacuum circuit breakers and associated secondary equipment.

Normal use environmental conditions
  • Ambient temperature: +40°C maximum, -10°C minimum (storage/transport down to -30°C with restrictions).
  • Relative humidity: daily average ≤ 95%, monthly average ≤ 90%.
  • Altitude: typically ≤ 1000 m (higher altitude available on request).
  • Seismic intensity: < 8 degrees.
  • Do not install in locations with fire/explosion hazard, heavy pollution, chemical corrosion or severe vibration.


Main technical parameters
  • Rated voltage (max operating): 3.6 / 7.2 / 12 kV
  • Rated current: 630–3150 A
  • Rated short-circuit breaking current options: 16, 20, 31.5, 40 kA
  • Rated short-circuit making current (peak): 40, 50, 80, 100 kA
  • Rated dynamic stability (peak): 40, 50, 80, 100 kA
  • Rated thermal stability current: 16, 20, 31.5, 40 kA; thermal stability time: 4 s
  • Protection level: IP3X
  • Busbar system: single busbar segmentation (single/double/bypass layouts available)
  • Operation method: electromagnetic or spring energy-storage drive
  • Typical dimensions (W×D×H): 1100 × 1200 × 2650 mm
  • Typical weight: approx. 1000 kg


Technical parameters of main electrical equipment (example: ZN28A-12 vacuum circuit breaker)
The main circuit-breaker and auxiliary devices used in XGN2-12 cabinets follow the same rated ranges: 3.6/7.2/12 kV, 630–3150 A, breaking capacities and dynamic/thermal stability values as listed above. Selection depends on application and required breaking/making ratings.

Structural characteristics
The cabinet is a metal-enclosed box divided into functional compartments separated by steel plates: circuit breaker compartment, busbar compartment, cable compartment and relay compartment. Key features include:
  • Circuit breaker compartment located front-lower with pull-rod linkage to the operating mechanism and pressure-relief channel for internal-arc gas discharge.
  • Busbar compartment at rear-upper with porcelain insulator supports and option for chamber segmentation.
  • Cable compartment rear-lower with cable fixing, support insulators and secondary device mounting provisions.
  • Relay compartment front-upper with mounting plate for relays, terminal blocks and space for secondary instruments.
  • Operating mechanisms arranged for front inspection and rear maintenance; front earth bus provided under the front door.
  • Mechanical interlocks implement five-prevention sequences to prevent unsafe operations.


Product appearance and structure
Outline drawings and typical assembly illustrations show compartment layout, component assemblies (support insulators, busbar assemblies, CT assembly, vacuum breaker drive) and door/access features that facilitate installation and service.

Operation and maintenance
  • Defined operating sequences for isolation, earthing and insertion/withdrawal of withdrawable units support safe maintenance procedures.
  • Accessible secondary terminals and internal lighting simplify inspection and testing.
  • Manufacturer guidance required for configuration, lifting and site installation.


Characteristics / technical specifications
  • Model: XGN2-12
  • Rated voltages: 3.6, 7.2, 12 kV
  • Rated current range: 630–3150 A
  • Breaking current options: 16, 20, 31.5, 40 kA
  • Making current (peak): 40, 50, 80, 100 kA
  • Thermal stability time: 4 s
  • Protection: IP3X
  • Typical dimensions: 1100 × 1200 × 2650 mm
  • Typical weight: ~1000 kg