Current switchgear XGN66-12
voltagefrequencythree-phase

Current switchgear - XGN66-12 - SAIP ELECTRIC GROUP CO.,LTD - voltage / frequency / three-phase
Current switchgear - XGN66-12 - SAIP ELECTRIC GROUP CO.,LTD - voltage / frequency / three-phase
Add to favorites
Compare this product

Characteristics

Electrical characteristics
short-circuit, frequency, voltage, medium-voltage, current, AC, three-phase, grounding, over-current
Configuration
metal-clad
Applications
for power plants, for electrical networks, power distribution
Other characteristics
fixed
Primary current

Max.: 1,250 A

Min.: 630 A

VAC

Max.: 12,000 V

Min.: 3,600 V

Description

Product overview
This XGN66-12 fixed metal-enclosed switchgear is a next-generation indoor high-voltage distribution assembly designed to meet GB3906, DLT404 and IEC60298 standards. The unit is compact (≈50% volume of a conventional cabinet) and is intended for single-bus segmentation at rated voltages 3.6, 7.2 and 12 kV. It is suitable for receiving and distributing electrical energy and for circuit control, protection and monitoring in power plants, substations, industrial/mining sites, high-rise buildings and ring-network stations.

Model meaning
  • Install vacuum circuit breaker
  • Rated voltage (kV)
  • Design number
  • Indoor use
  • Withdrawable option
  • Armoured / metal-enclosed


Normal use environmental conditions
  • Ambient temperature: -25°C to +40°C (24 h average ≤ +35°C)
  • Altitude: ≤ 1000 m
  • Horizontal inclination: ≤ 3°
  • Seismic intensity: ≤ 8
  • No severe vibration, shock or explosive atmosphere


Structural features
  • Cabinet body welded from high-quality angle steel
  • Circuit-breaker compartment located centrally (or lower) for easy installation, commissioning and maintenance; standard provision for ZN63A (VS1-12) breaker and pressure-release channel
  • Advanced rotary isolating switch allowing safe access to breaker compartment with main bus energized
  • Overall protection level: IP4X
  • Compulsory mechanical locking device fulfilling 'five preventions' interlock requirements
  • Reliable grounding system and clear grounding provision
  • Front door with observation window for visual inspection of components
  • Operating mechanism with JSXGN-type locking compatible with XGN12-12 models
  • Incoming/outgoing cables enter from lower front of cabinet for convenient connection


Main technical parameters (general)
  • Rated voltages: 3.6, 7.2, 12 kV
  • Rated frequency: 50 Hz
  • Rated currents: 630 A, 1250 A
  • Rated short-circuit breaking current (Ieff): 20 kA, 25 kA, 31.5 kA
  • Rated short-circuit making current (peak): 50 kA, 63 kA, 80 kA
  • Rated short-time withstand current (4 s): 20 kA, 25 kA, 31.5 kA
  • Rated lightning impulse withstand voltage: up to 75/85 kV (to ground/phase)
  • Rated power frequency withstand voltage: up to 42/48 kV (to ground/phase)
  • Protection level: IP4X
  • Dimensions (W × D × H): 900 × 1000 × 2300 mm (typical)
  • Approx. weight: ≈ 600 kg


Main technical parameters (12 kV / breaker)
  • Rated voltage: 12 kV
  • Rated current: 630 A, 1250 A
  • Rated short-circuit breaking current: 20 kA, 25 kA, 31.5 kA
  • Rated short-circuit making current (peak): 50 kA, 63 kA, 80 kA
  • Rated short-time withstand current (4 s): 20 kA, 25 kA, 31.5 kA
  • Rated peak withstand current: 50 kA, 63 kA, 80 kA
  • Mechanical life: 10,000 operations
  • Rated breaking times (short-circuit operations): 50
  • Rated operating sequence: 0.3 s - 180 s
  • Contact opening distance: 11 ± 1 mm; contact stroke: 4 ± 0.5 mm
  • Phase center distance: 210 mm
  • Opening speed ≈ 41.2 ± 0.2 m/s; closing speed ≈ 0.6 ± 0.2 m/s
  • Opening time ≤ 60 ms; closing time ≤ 75 ms; three-phase synchronization ≤ 2 ms
  • Loop resistance ≤ 45 μΩ; contact allowable wear thickness 3 mm


Install
  • Refer to foundation drawing: foundation channel steel should protrude 1–3 mm; unevenness ≤ 1.5 mm/m, total deviation ≤ 5 mm
  • Place cabinet on foundation, adjust position and fix with M12 bolts or spot welding; tighten cabinet with M8 bolts
  • After removing covers, install main busbar and primary cables; clean contact surfaces and coat with neutral petroleum jelly; seal cable holes after installation
  • Connect indirect ground bus along arrangement direction; ensure continuity of working and protective grounding; working grounding resistance must meet equipment specification
  • Install secondary cables from the lower front to the low-voltage compartment or via the small secondary bus on top; seal cable holes after installation
  • Clean dust and debris from cabinet after installation


Put into operation
  • Before operation verify models and specifications of installed components; check for loose fasteners; verify primary and secondary wiring
  • Operate isolating switch, grounding switch and circuit breaker 3–5 times to ensure free movement and correct mechanical interlocking; lubricate moving parts as needed
  • Check insulation level, loop resistance and mechanical characteristics of circuit breaker against factory test reports; test results should be consistent with factory values


Documents and attachments
  • Product qualification certificate and packing list
  • Installation instructions and secondary wiring diagrams for the switchgear and main components
  • Energy storage device and operating handle (included accessories)


Order notice
  • Provide wiring plan and wiring arrangement diagrams
  • Provide secondary circuit schematic, wiring diagram and terminal arrangement
  • Provide list of primary and secondary equipment
  • Provide layout of switchgear and installation position for busbar tray


Characteristics / technical specifications
  • Rated voltages: 3.6, 7.2, 12 kV
  • Rated frequency: 50 Hz
  • Rated currents: 630 A, 1250 A
  • Short-circuit breaking current (Ieff): 20 / 25 / 31.5 kA
  • Short-circuit peak current (Ipk): 50 / 63 / 80 kA
  • Short-time withstand (4 s): 20 / 25 / 31.5 kA
  • Protection level: IP4X
  • Dimensions (W×D×H): 900 × 1000 × 2300 mm
  • Approx. weight: ≈ 600 kg
  • Breaker mechanical life: 10,000 operations
  • Contact opening distance: 11 ± 1 mm; contact stroke: 4 ± 0.5 mm
  • Opening time ≤ 60 ms; closing time ≤ 75 ms; three-phase synchronization ≤ 2 ms
  • Loop resistance ≤ 45 μΩ; allowable contact wear thickness: 3 mm