Current switchgear KYN28A-12
voltagefrequencythree-phase

Current switchgear - KYN28A-12 - SAIP ELECTRIC GROUP CO.,LTD - voltage / frequency / three-phase
Current switchgear - KYN28A-12 - SAIP ELECTRIC GROUP CO.,LTD - voltage / frequency / three-phase
Current switchgear - KYN28A-12 - SAIP ELECTRIC GROUP CO.,LTD - voltage / frequency / three-phase - image - 2
Add to favorites
Compare this product

Characteristics

Electrical characteristics
frequency, voltage, medium-voltage, current, three-phase
Configuration
metal-clad, vacuum
Applications
for electrical networks, power distribution
Other characteristics
draw-out
Primary current

Min.: 630 A

Max.: 4,000 A

VAC

Min.: 3,600 V

Max.: 12,000 V

Description

Product overview
The KYN28A-12(Z)(GZS1) is an armored, withdrawable, metal-enclosed AC switchgear designed for three-phase 50 Hz power systems. It is used for receiving and distributing electrical energy and for control, protection and monitoring of circuits. The product complies with GB3906, GB/T11022, IEC60298 and DL/T404.

Model meaning
  • Equipped for vacuum circuit breaker installation
  • Rated voltage (kV)
  • Design/version identifier
  • Indoor application
  • Withdrawable (handcart) design
  • Armored/metal-enclosed


Normal use conditions
  • Ambient temperature: max +40°C, min -15°C
  • Humidity: daily average relative humidity ≤95% (daily vapor pressure ≤2.2 kPa); monthly average ≤90% (monthly vapor pressure ≤1.8 kPa)
  • Altitude: ≤1000 m
  • Seismic intensity: ≤ 8
  • Environment free of significant corrosive/combustible gases and excessive water vapor
  • No frequent severe vibration
  • Use beyond GB3906 conditions requires agreement between user and manufacturer


Key technical parameters
Rated voltage: 3.6, 7.2, 12 kV
Rated frequency: 50 Hz
Circuit breaker rated currents: 630, 1250, 1600, 2000, 2500, 3150, 4000 A
Switchgear rated currents: 630–4000 A (same stages)
Short-time withstand current (4 s): 16, 20, 25, 31.5, 40, 50 kA
Peak withstand current (peak): 40, 50, 63, 80, 100 kA (per configuration)
Rated short-circuit breaking current: 16–50 kA
Insulation levels (1 min power frequency withstand): 24, 32, 42 kV
Lightning impulse withstand (peak): 40, 60, 75 kV
Protection degree: enclosure IP4X (IP3X when adjacent compartment and breaker room doors are open)


Product structure characteristics
  • Fully metal-armored, modular assembly structure with wide combination options
  • Cabinet: aluminium-zinc coated thin steel plate, multi-folded and fixed by rivet nuts and high-strength bolts for precision and strength
  • Compatible with VS1-12 or VD4 series vacuum circuit breakers (or equivalents) for broad applicability
  • Handcart (withdrawable unit) with work and test positions; each position has positioning and indication devices
  • Modular handcarts are interchangeable within the same specification; different specifications are not interchangeable
  • Earthing switch can be front-mounted (central) for two-sided maintenance or rear-mounted to save space
  • Current transformers installed in rear cable compartment; cable room accommodates up to 9 single-core cables
  • Each high-voltage chamber includes a pressure-relief channel; reliable interlock meets five-prevention safety requirements
  • Front and rear doors include observation windows; handcart transport via special carrier for safe operation


Diagram / component list
A. Busbar room
B. Circuit breaker handcart room
C. Cable room
D. Relay/instrument room
1. Shell
2. Branch bus
3. Bus bushing
4. Main bus
5. Static contact device
6. Contact box
7. Current transformer
8. Earthing switch
9. Cable
10. Lightning arrester
11. Ground bus
12. Loading/unloading partitions
13. Partition (trap)
14. Secondary plug
15. Circuit breaker handcart
16. Heating device
17. Withdrawable horizontal partition
18. Ground operating mechanism
19. Bottom plate
20. Pressure relief device
21. Control wire duct


Dimensions (typical)
Cabinet height (B): 2300 (2200) mm
Height A (for branch busbar rated current ≤1250 A): 800 (650) mm; for ≥1600 A: 1000 mm
Height C (cable inlet/outlet): 1500 mm; overhead incoming/outgoing: 1660 mm
Cabinet width examples (A): 800 / 1000 mm
Cabinet depth examples (B): 1500 mm (cable) or 1660 mm (overhead) — L1–L4 vary per configuration


Order notice
  • Provide main circuit diagram number, intended purpose and single-line system diagram, rated voltage, rated current and rated short-circuit breaking current
  • Submit distribution room layout and switchgear arrangement drawings
  • Specify required control, measurement and protection functions, interlocks and automation
  • Indicate model, specifications and quantities of main electrical components
  • If busbar bridges are required, specify rated current capacity, span, height above ground and other details
  • Specify any special environmental conditions or other special requirements


Technical specifications (summary)
  • Model: KYN28A-12
  • Type: Armored withdrawable metal-enclosed switchgear
  • Rated voltage: 3.6 / 7.2 / 12 kV
  • Rated frequency: 50 Hz
  • Rated currents (breaker & switchgear): 630, 1250, 1600, 2000, 2500, 3150, 4000 A
  • Short-time withstand (4 s): 16–50 kA
  • Peak withstand currents and breaking capacities per configuration (see parameters)
  • Insulation and impulse withstand levels: multiple kV levels as listed
  • Protection: IP4X (closed); IP3X when doors open
  • Construction: aluminium-zinc coated steel, modular, handcart withdrawable, safety interlocks and pressure relief channels