Product overviewThe XGN15-12 box-type, fixed, metal-enclosed ring main unit is an SF6-based load switch / load-switch-fuse combination switchgear designed for 12 kV distribution networks. Air-insulated and modular, it delivers a compact, automated and extendable solution for ring network and terminal supply in urban, industrial and commercial installations. Compliant with GB3804, GB3906, GB16926, GB/T11022 and IEC420.
Applications- Ring-main distribution and terminal supply in urban and municipal power grids
- Power distribution for industrial and mining sites
- High-rise buildings, residential complexes, hospitals, schools and parks
- Compact/nearby substations and retrofit projects
Environmental conditions- Ambient temperature: max +40 °C, min -15 °C, daily average ≤ 35 °C
- Relative humidity: daily average ≤ 95%, monthly average ≤ 90% (vapor pressure limits as specified)
- Altitude: ≤ 1000 m; seismic intensity ≤ 8
- Installation site: no dripping water, no explosive/flammable atmosphere, no chemically corrosive gases, no violent vibration
Main technical parameters- Model: XGN15-12; Rated voltage: 12 kV; Main bus rated current: 630 A
- Rated current: load switch up to 630 A; combined unit example 125 A
- Rated frequency: 50 Hz; Short-time withstand current (example): 20 kA; Duration: 3 s; Peak withstand: up to 50 kA
- Rated short-circuit breaking current: up to 31.5 kA (combined)
- Rated short-circuit making current: up to 50 kA (load switch) / 80 kA (combined)
- Cable charging breaking current: 10 A; Example transfer current: 1700 kA
- Insulation levels: 1 min power frequency to ground/phase 42 kV (rupture 48 kV); Lightning impulse withstand: 15 kV (rupture 85 kV)
- Main circuit resistance: ≤ 300; Mechanical life: ~2000 operations; Protection degree: IP4X
Structural featuresMetal-enclosed box divided into upper compartments (busbar room, switch room, low-voltage/control room) and lower cable room to isolate functions, improve safety and simplify maintenance. Typical overall dimensions: 375 × 960 × 1600 mm and 500 × 960 × 1600 mm.
- Cable room: space for single- or three-core cables; accommodates fuses, surge arresters, CTs, grounding switch; cabinet door with observation window and safety interlock; removable cable cover and clamp options
- Switch room: accepts a three-position load switch; epoxy shell filled with SF6; provision for observation window and gas density monitor/relay with alarm contacts
- Busbar room: horizontal three-phase main busbar running through cabinet row
- Low-voltage room: control panel with spring operating mechanism, position indicator, mechanical interlock; optional auxiliary contacts, trip coils, emergency trip, key lock and electric operation
Operation and interlock- Operation modes: manual handle on front panel; optional electric open/close buttons; if electric drive absent, manual operation possible. Grounding switch is manual only
- Interlock logic: prevents unsafe operations (e.g., when load switch is closed, grounding switch cannot close and lower door cannot open; blown phase fuse forces load switch to open and prevents reclosing)
Installation and diagramsSchematic installation, foundation drawings and cable inlet/outlet layout figures are provided for recommended layout, cable routing and mounting dimensions. Refer to product documentation for detailed installation diagrams.
Compliance and standards- Applicable standards: GB3804, GB3906, GB16926, GB/T11022, IEC420
- Typical ratings: 12 kV, 50 Hz, IP4X, altitude ≤ 1000 m