GeneralXGN (XGTD5)-(12,24)40.5 series indoor gas-insulated metal-clad switchgear (C-GIS panel) integrates a spring-operated vacuum circuit breaker, electrically operated three-position isolation/earthing switch, transformer and lightning arrester. All high-voltage conductors are sealed inside a metal-clad enclosure filled with SF6 as the insulating medium. The design enables flexible configurations, complete interlocking logic, easy extensibility and reduced maintenance. Typical uses include power plants, substations, mobile transformer units, rail traction and building distribution up to 35 kV, including harsh environments (high altitude, heavy pollution, high humidity).
Service conditions- Ambient temperature: -45 °C to +40 °C; daily average must not exceed 35 °C.
- Altitude: below 5000 m above sea level.
- Relative humidity: daily average < 95%; monthly average < 90%.
- Seismic intensity: not to exceed grade 8.
- Inductive electromagnetic interference of secondary system: ≤ 1.6 kV.
Main technical parameters- Model family: XGN (XGTD5)
- Rated voltage options: 12 kV / 24 kV / 40.5 kV
- Rated current options: 630 A, 1250 A, 1600 A, 2000 A, 2500 A, 3150 A
- Rated frequency: 50 / 60 Hz
- 1 min power-frequency withstand voltage (RMS) phase-phase / phase-earth: 42 / 65 / 95 kV
- Insulation distances (power-frequency / impulse): 48 / 79 / 118 mm and 85 / 145 / 215 mm (by voltage)
- Rated lightning impulse withstand voltage (peak) phase-phase / phase-earth: 75 / 125 / 185 kV
- Rated short-circuit breaking current (RMS): 20 / 25 / 31.5 / 40 kA; making current (peak): 50 / 63 / 80 / 100 kA
- Rated short-time withstand current (4 s): 20 / 25 / 31.5 / 40 kA
- Auxiliary/control circuit rated voltage: DC110/220, AC220
- SF6 rated pressure (20 °C): 0.04 / 0.05 MPa; min pressure: 0.03 MPa; annual gas loss ≤ 5‰
- Degree of protection: HV compartment IP67; LV compartment IP4X
- Approx. weight: 1000–1600 kg (depending on configuration)
Main technical parameters of vacuum circuit breaker- Rated voltage: 12 / 24 / 40.5 kV
- Rated current: 630–3150 A (options)
- Rated frequency: 50 / 60 Hz
- 1 min power-frequency withstand voltage (RMS): 42 / 65 / 95 kV
- Rated lightning impulse withstand voltage (peak): 75 / 125 / 185 kV
- Rated short-circuit breaking current (RMS): 20 / 25 / 31.5 / 40 kA
- Rated making current (peak): 50 / 63 / 80 / 100 kA
- Rated short-time withstand current (4 s): 20 / 25 / 31.5 / 40 kA
- Mechanical life: 10,000 operations
- Rated operating sequence: 0-0.3s-CO-3min-CO
- Contact open clearance: 9 ±1 / 13 ±1 / 18 ±1 mm (by rating)
- Contact bounce time on closing: ≤ 2 ms; three-phase asynchrony ≤ 2 ms
- Main circuit resistance per phase (vacuum breaker): ≤ 25 μΩ
- Energy storage time of closing spring: ≤ 15 s
StructureThe typical cabinet layout includes bus panel, meter panel, circuit breaker panel, cable panel, mechanism panel and associated components such as outer/inner cone bushings, gas tank, branch bus, pressure-relief devices, CT (ring-core or built-in), gas density relay, three-position switch operating mechanism and secondary unit/front panels.
- Front panel
- Framework
- Back panel
- HV cable (user-supplied)
- Back-plug type lightning arrester
- CT (ring-core type)
- Outer/inner cone bushings (connections)
- Vacuum circuit breaker
- Gas tank
- Branch bus and main bus
- Pressure relief devices
- Three-position DS/ES and operating mechanism
- Gas density relay
- Secondary unit panel
Applications & specifications- Intended for medium-voltage indoor distribution up to 35 kV: power plants, substations, mobile transformer units, rail traction, industrial and commercial buildings
- Supports rated currents 630–3150 A and breaking capacities up to 40 kA (RMS) with peak making up to 100 kA
- SF6 insulated, typical operating pressure 0.04–0.05 MPa at 20 °C; annual leak rate ≤ 5‰
- HV compartment IP67 provides protection for harsh environments; modular and extendable configurations
- Vacuum breaker mechanical life ≈ 10,000 operations