GeneralThe XGN (XGTD6)-12(24) indoor gas‑insulated metal‑enclosed switchgear is a medium‑voltage SF6‑insulated assembly designed for secondary distribution and compact substation applications. It features a modular layout, sealed stainless‑steel gas tanks for primary live parts, and front access for cables and controls to facilitate installation and operation.
StandardsDesign and quality comply with current international and national standards. Typical references include:
IEC62271-200
EN50181
GB/T3906
GB/T11022
DL/T404
GB/T1984
GB/T1985
GB/T20840
GB/T11032
Type and designation / Typical applicationsModular indoor gas‑insulated metal‑enclosed switchgear suitable for secondary distribution substations, box‑type substations, industrial and mining plants, airports, railways, commercial buildings, high‑rise buildings, highways, subways and tunnels. Units can be combined as fixed common‑box or expandable modules to match site layouts and network schemes.
Service conditions- Ambient temperature: -45°C to +50°C (daily average ≤ 35°C).
- Relative humidity: daily average ≤ 95%; monthly average ≤ 90%.
- Altitude: ≤ 4000 m (specify if > 1000 m for manufacturing adjustments).
- Seismic intensity: up to grade 8.
- No corrosive, flammable gases or harmful pollution in the installation environment.
Technical parameter (selected)Rated voltage (kV): 12 / 24
Rated frequency (Hz): 50 / 60
Rated current (A): 630, 1250 (depending on configuration)
Rated insulation level (1 min power frequency withstand) (kV): 42 / 65 (phase‑phase / phase‑earth)
Insulation distance (kV): 48 / 79
Lightning impulse withstand voltage (kV): 75 / 125
Rated short‑time withstand current (kA/s): 20/4, 25/4
Rated peak withstand current (kA): 50, 63
Rated transfer current (A): 1700 / 1400 (specific configs)
SF6 nominal inflation pressure (MPa at 20°C): 0.04
Annual SF6 loss rate: ≤ 0.05%
Protection degree: cabinet IP4X; gas chamber IP67
Mechanical life (operations): load switch / circuit breaker 5000 / 10000
Product features and structure- Modular design enabling flexible unit combinations and on‑site expansion (load switch, load switch+fuse, circuit breaker, metering unit, bus PT, etc.).
- Fully sealed stainless‑steel SF6 gas tanks enclosing primary live parts for dielectric and environmental protection.
- External connections via standard DIN47636 bushings or fully insulated separable connectors; gas chamber rated to IP67 to resist short flooding and condensation.
- Reliable pressure relief device, dedicated relief channels and mechanical interlocks to prevent misoperation and enhance safety.
- Maintenance reduction provided by sealed SF6 insulation and maintenance‑free vacuum arc interrupters.
- Front‑access interface and clear operation panel for convenient cable routing, inspection and reduced operator errors.
- Adapted to harsh environments: high altitude, extreme cold, high humidity, salt spray and polluted atmospheres.
Product structure and outline- Barometer
- Load switch operating hole
- Earthing switch operating hole
- Air box compartment
- View window
- Pressure relief chamber
- Cable room (front door)
- Disconnector
- Circuit breaker energy storage operation hole
- Built‑in fuse
- Live indication
- Secondary instrument room
Outline dimensions / number of unitsNumber of units — Width W (mm): 1 — 375; 2 — 700; 3 — 1025; 4 — 1350; 5 — 1675; 6 — 2000.
Standard module reference: W × 750 × 1600 mm; additional unit width interval 325 mm. Height 1600 mm excludes secondary instrument room; height of instrument room adjustable as required.
Characteristics / technical specifications- Model family: XGN (XGTD6).
- Rated voltage: 12 / 24 kV.
- Rated frequency: 50 / 60 Hz.
- Rated current options: 630 A, 1250 A.
- Dielectric levels: 1 min power frequency 42/65 kV; lightning impulse 75/125 kV.
- Short‑circuit performance: peak 50/63 kA; short‑time withstand 20/4 or 25/4 kA/s.
- SF6 nominal pressure: 0.04 MPa (20°C); annual leakage ≤ 0.05%.
- Protection: cabinet IP4X; gas chamber IP67.
- Loop resistance ≤ 150 µΩ where applicable.
- Mechanical life: load switch 5000 operations, circuit breaker up to 10000 operations.