Frequency switchgear XGN (XGTD6)-12(24)
three-phaseACmedium-voltage

Frequency switchgear - XGN (XGTD6)-12(24) - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage
Frequency switchgear - XGN (XGTD6)-12(24) - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage
Frequency switchgear - XGN (XGTD6)-12(24) - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage - image - 2
Frequency switchgear - XGN (XGTD6)-12(24) - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage - image - 3
Frequency switchgear - XGN (XGTD6)-12(24) - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage - image - 4
Add to favorites
Compare this product

Characteristics

Electrical characteristics
insulated, medium-voltage, frequency, AC, compact, three-phase
Configuration
gas-insulated, SF6 gas-insulated, SF6
Applications
industrial, for electrical networks, power distribution, for railway applications
Other characteristics
modular
Primary current

125 A, 630 A, 1,250 A

VAC

220 V

VDC

110 V, 220 V

Description

General
The XGN (XGTD6)-12(24) indoor gas‑insulated metal‑enclosed switchgear is a medium‑voltage SF6‑insulated assembly designed for secondary distribution and compact substation applications. It features a modular layout, sealed stainless‑steel gas tanks for primary live parts, and front access for cables and controls to facilitate installation and operation.

Standards
Design and quality comply with current international and national standards. Typical references include:
IEC62271-200
EN50181
GB/T3906
GB/T11022
DL/T404
GB/T1984
GB/T1985
GB/T20840
GB/T11032

Type and designation / Typical applications
Modular indoor gas‑insulated metal‑enclosed switchgear suitable for secondary distribution substations, box‑type substations, industrial and mining plants, airports, railways, commercial buildings, high‑rise buildings, highways, subways and tunnels. Units can be combined as fixed common‑box or expandable modules to match site layouts and network schemes.

Service conditions
  • Ambient temperature: -45°C to +50°C (daily average ≤ 35°C).
  • Relative humidity: daily average ≤ 95%; monthly average ≤ 90%.
  • Altitude: ≤ 4000 m (specify if > 1000 m for manufacturing adjustments).
  • Seismic intensity: up to grade 8.
  • No corrosive, flammable gases or harmful pollution in the installation environment.


Technical parameter (selected)
Rated voltage (kV): 12 / 24
Rated frequency (Hz): 50 / 60
Rated current (A): 630, 1250 (depending on configuration)
Rated insulation level (1 min power frequency withstand) (kV): 42 / 65 (phase‑phase / phase‑earth)
Insulation distance (kV): 48 / 79
Lightning impulse withstand voltage (kV): 75 / 125
Rated short‑time withstand current (kA/s): 20/4, 25/4
Rated peak withstand current (kA): 50, 63
Rated transfer current (A): 1700 / 1400 (specific configs)
SF6 nominal inflation pressure (MPa at 20°C): 0.04
Annual SF6 loss rate: ≤ 0.05%
Protection degree: cabinet IP4X; gas chamber IP67
Mechanical life (operations): load switch / circuit breaker 5000 / 10000

Product features and structure
  • Modular design enabling flexible unit combinations and on‑site expansion (load switch, load switch+fuse, circuit breaker, metering unit, bus PT, etc.).
  • Fully sealed stainless‑steel SF6 gas tanks enclosing primary live parts for dielectric and environmental protection.
  • External connections via standard DIN47636 bushings or fully insulated separable connectors; gas chamber rated to IP67 to resist short flooding and condensation.
  • Reliable pressure relief device, dedicated relief channels and mechanical interlocks to prevent misoperation and enhance safety.
  • Maintenance reduction provided by sealed SF6 insulation and maintenance‑free vacuum arc interrupters.
  • Front‑access interface and clear operation panel for convenient cable routing, inspection and reduced operator errors.
  • Adapted to harsh environments: high altitude, extreme cold, high humidity, salt spray and polluted atmospheres.


Product structure and outline
  • Barometer
  • Load switch operating hole
  • Earthing switch operating hole
  • Air box compartment
  • View window
  • Pressure relief chamber
  • Cable room (front door)
  • Disconnector
  • Circuit breaker energy storage operation hole
  • Built‑in fuse
  • Live indication
  • Secondary instrument room


Outline dimensions / number of units
Number of units — Width W (mm): 1 — 375; 2 — 700; 3 — 1025; 4 — 1350; 5 — 1675; 6 — 2000.
Standard module reference: W × 750 × 1600 mm; additional unit width interval 325 mm. Height 1600 mm excludes secondary instrument room; height of instrument room adjustable as required.

Characteristics / technical specifications
  • Model family: XGN (XGTD6).
  • Rated voltage: 12 / 24 kV.
  • Rated frequency: 50 / 60 Hz.
  • Rated current options: 630 A, 1250 A.
  • Dielectric levels: 1 min power frequency 42/65 kV; lightning impulse 75/125 kV.
  • Short‑circuit performance: peak 50/63 kA; short‑time withstand 20/4 or 25/4 kA/s.
  • SF6 nominal pressure: 0.04 MPa (20°C); annual leakage ≤ 0.05%.
  • Protection: cabinet IP4X; gas chamber IP67.
  • Loop resistance ≤ 150 µΩ where applicable.
  • Mechanical life: load switch 5000 operations, circuit breaker up to 10000 operations.

Catalogs

No catalogs are available for this product.

See all of Ningbo Tianan (Group) CO.,Ltd.‘s catalogs
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About DirectIndustry
DirectIndustry is a marketplace that offers B2B players a complete experience, from product sourcing to purchase. DirectIndustry is an entity of VirtualExpo Group.