GeneralThe XGN(XGTD10)-40.5 is an indoor gas-insulated metal-enclosed switchgear that seals high-voltage components such as vacuum circuit breakers, isolating switches, load switches and fused units inside an SF6-filled stainless-steel gas tank. Its modular design supports common or expandable units and multiple main wiring schemes. Suitable for 35 kV ring networks and radial feeders where compact footprint and high reliability are required; typical applications include industrial, commercial and residential distribution, prefabricated substations, compact cabin stations and wind-turbine towers.
Quality assuranceProduct quality relies on continuous R&D and controlled manufacturing processes. Units are supplied in compliance with current international and national standards and factory test procedures.
Standards and complianceCompliant with IEC62271-200, EN50181, GB/T3906, GB/T11022, DL/T404, GB/T1984, GB 3804, GB 1985, GB 16926 and related specifications.
Service conditions- Ambient temperature: -25°C to +40°C (daily average ≤ +35°C)
- Relative humidity: daily avg ≤ 95%, monthly avg ≤ 90%
- Altitude ≤ 3000 m; seismic intensity ≤ level 8
- No significant corrosive or flammable gas pollution at site
Technical parameters (key data)Rated voltage: 36/40.5 kV. Rated frequency: 50/60 Hz. Main bus rated current: 1250 A. Branch bus typical: 630 A (branch and fuse dependent). Power-frequency withstand (1 min, rms) phase-phase/phase-earth: 70/95 kV. Lightning impulse withstand (peak): 170/185 kV. Short-time withstand example: 20 kA/3 s; rated peak withstand example: 50 kA. SF6 nominal pressure (20°C): 0.05 MPa; min 0.03 MPa. Annual SF6 leakage ≤ 0.1%. Degree of protection: HV compartment IP67; LV compartment IP4X. Cabinet outline (single): 500 × 885 × 2060 mm; common cabinet example 465 × 885 × 2060 mm; up to 6 common boxes, width increment 465 mm.
Main switch parameters (summary)Rated voltage: 36/40.5 kV. Rated current example: 630 A (depends on configuration). Withstand voltages and currents as listed above. Main circuit resistance per phase: device dependent, typical values ≤ 70 μΩ. Mechanical life examples: load switch/CB ~3000 cycles; some CB types up to 5000 cycles.
Features and structure- Modular design for flexible combination and expansion (C, F, V, M, PT units etc.).
- Primary live parts and switch body sealed in SF6 gas tank; DIN47636-compliant bushings; gas chamber protection to IP67.
- Pressure relief devices and channels plus full mechanical interlocks to prevent misoperation.
- Compact footprint, reduced maintenance due to vacuum switching technology and long service life.
- Adapted for demanding environments: high altitude, low temperature, high humidity, salt spray and pollution.
Product structure and compartmentsThe switchgear comprises a gas chamber and cabinet frame with four main compartments: instrument compartment, switch (gas) compartment, mechanism compartment and cable compartment. Front-mounted secondary instruments and visible operation positions; switch compartment bottom includes pressure relief channel.
Illustrated components- Gas-pressure gauge
- Load-switch operation hole
- Observation window
- Pressure-relief chamber
- Cable compartment (front door)
- Isolation-switch operation hole
- Built-in fuse
- CB energy-storage operation hole
- CB open/close button
- Secondary instrument room
Characteristics / specifications- Model series: XGN(XGTD10)
- Rated voltage: 36/40.5 kV
- Rated frequency: 50/60 Hz
- Main bus rated current: 1250 A
- Branch bus rated current: 630 A (typ.)
- SF6 nominal pressure: 0.05 MPa (20°C); min 0.03 MPa
- Annual SF6 leakage: ≤ 0.1%
- Withstand voltages: power frequency 70/95 kV; lightning impulse 170/185 kV
- Short-time withstand example: 20 kA/3 s; peak example: 50 kA
- Protection degree: HV IP67; LV IP4X
- Cabinet dims single: 500 × 885 × 2060 mm; common cabinet: 465 × 885 × 2060 mm