Characteristics

Electrical characteristics
voltage, medium-voltage, frequency, current, AC, insulation, three-phase
Configuration
metal-clad, gas-insulated, SF6
Applications
circuit breaker, for power plants, for electrical networks, power distribution
Other characteristics
fixed, stationary
Primary current

Max.: 2,500 A

Min.: 630 A

VAC

220 V

VDC

110 V, 220 V

Description

General
XGTD7-(12/24)40.5 series indoor gas-insulated metal-clad switchgear (C-GIS cabinet) integrates a spring-operated vacuum circuit breaker, electrically operated three-position isolation/earthing switch, CT/PT and lightning arresters as main components. High-voltage conductors are fully sealed inside a metal-clad enclosure using gas as the insulating medium. The design enables flexible configurations, complete interlocking logic, easy extension, compact footprint and simplified maintenance. Typical applications: power plants, substations, mobile transformer units and buildings with nominal voltage ≤ 35 kV, including harsh environments (high altitude, heavy pollution, high humidity).

Service conditions
  • Ambient temperature: -25°C to +40°C (daily average ≤ 35°C)
  • Altitude: ≤ 5000 m above sea level (specify if > 1000 m for pressure setting at production)
  • Relative humidity: daily average ≤ 95%; monthly average ≤ 90%
  • Seismic intensity: ≤ grade 8
  • Electromagnetic interference amplitude induced by secondary systems: ≤ 1.6 kV


Technical parameters
Main technical parameters:
Rated voltage — 12 / 24 / 40.5 kV
Rated current — 630 / 1250 / 1600 / 2000 / 2500 A
Rated frequency — 50 / 60 Hz
1 min rated power-frequency withstand voltage (RMS), Phase-Phase / Phase-Earth — 12 kV: 42 (insulation fracture 48); 24 kV: 65 (79); 40.5 kV: 95 (118) kV
Rated lightning impulse withstand voltage (peak), Phase-Phase / Phase-Earth — 12 kV: 75 (insulation fracture 85); 24 kV: 125 (145); 40.5 kV: 185 (215) kV
Auxiliary circuit power-frequency withstand voltage — 2 kV
Rated short-circuit breaking current (r.m.s) — 20 / 25 / 31.5 kA
Rated short-circuit making current (peak) — 50 / 63 / 80 kA
Rated short-time withstand current (4 s) — 20 / 25 / 31.5 kA
Main circuit resistance per phase — Rc ≤ 200 mΩ (rated current ≤ 1600 A); Rc ≤ 105 mΩ (rated current ≥ 2000 A)
Auxiliary/control voltage — DC110/220, AC220 V
Rated working pressure of insulation gas (20°C) — nominal 0.05 MPa; minimum 0.03 MPa
Annual gas loss rate — ≤ 5 ‰
Degree of protection — HV gas compartment IP67; LV compartment IP4X
Weight — 1000–1600 kg

Typical scheme
Typical structure and outline dimensions. Labels: A – Cable room; B – Main switch room; C – Instrument room; D – Mechanism room. Typical cabinet examples: XGTD7-40.5/1250 circuit breaker cabinet (bus top expansion) and XGTD7-40.5/1250 circuit breaker cabinet (bus side expansion).

Characteristics / specifications
  • Series: XGTD7
  • Product type: Indoor gas-insulated metal-clad switchgear (C-GIS cabinet)
  • Main components: spring-operated vacuum circuit breaker, electrically operated three-position isolation/earthing switch, CT/PT, lightning arrester
  • Insulating medium: gas (SF6 or equivalent depending on version)
  • Rated voltages: 12 / 24 / 40.5 kV
  • Rated currents available: 630 / 1250 / 1600 / 2000 / 2500 A
  • Rated frequency: 50 / 60 Hz
  • Short-circuit breaking current options (r.m.s): 20 / 25 / 31.5 kA
  • Making current (peak): 50 / 63 / 80 kA
  • Auxiliary/control voltage: DC110/220 and AC220 V
  • Insulation gas working pressure (20°C): nominal 0.05 MPa, minimum 0.03 MPa
  • Annual gas loss rate: ≤ 5 ‰
  • Protection: HV gas compartment IP67; LV compartment IP4X
  • Approximate weight: 1000–1600 kg