OverviewThe KYN28A air‑insulated withdrawable metal‑clad switchgear (KYN28A series) is a complete distribution assembly for 12 kV and 24 kV three‑phase AC single busbar and segmented single busbar systems. It is intended for power plants, substations, industrial and mining sites and tall buildings for power transformation, reception/distribution, control, protection and line monitoring.
Standards and designThe design complies with IEC62271 series and GB/T standards for metal‑clad switchgear. Key referenced standards include IEC62271‑200, IEC62271‑100, GB/T3906, GB/T11022, GB/T1984 and DL/T404.
Interlocks and safety- Mechanical and electrical interlocks to prevent withdrawing/inserting the breaker under load
- Interlocks to avoid accidental opening/closing of the circuit breaker
- Locking to prevent closing the circuit breaker when the earthing switch is closed
- Measures to prevent accidental access to live compartments
Configurations and main componentsThe switchgear is mid‑mounted, metal‑clad and air‑insulated. Mid‑mounted withdrawable units (handcarts) are available for: circuit breakers, contactors, load switches, isolators, PTs, metering, fuses, lower PT, lower lightning arresters, etc. Main components include busbars, branch busbars, current transformers, earthing switch, pressure relief device, static contact box, secondary plug devices and removable panels.
Technical dataKYN28A‑12Rated voltage: 12 kV
Rated frequency: 50/60 Hz
1 min power‑frequency withstand voltage (phase‑to‑phase): 42/48 kV
Lightning impulse withstand voltage: 75/85 kV
Auxiliary circuit 1 min withstand voltage: 2000 V
Rated currents: 630, 1250, 1600, 2000, 2500, 3150, 4000, 5000 A
Rated short‑circuit breaking current (r.m.s): 20, 25, 31.5, 40, 50 kA
Rated short‑circuit making (peak): 50, 63, 80, 100, 125 kA
KYN28A‑24Rated voltage: 24 kV
Rated frequency: 50/60 Hz
1 min power‑frequency withstand voltage (phase‑to‑phase): 65/79 kV
Lightning impulse withstand voltage: 125/145 kV
Auxiliary circuit 1 min withstand voltage: 2000 V
Rated currents: 630, 1250, 1600, 2000, 2500, 3150 A
Rated short‑circuit breaking current (r.m.s): 20, 25, 31.5 kA
Rated short‑circuit making (peak): 50, 63, 80 kA
Dimensions and coolingTypical overall heights: 2320 mm (12 kV) and 2380 mm (24 kV). Width and depth depend on configuration (examples: 650/800/1000 mm widths for 12 kV; 800/1000 mm widths for 24 kV). Weight range: approx. 700–1400 kg depending on variant. Note: forced air cooling required for rated currents ≥ 4000 A (12 kV) or as specified.
Applications- Power plants and substations
- Industrial and mining distribution networks
- High‑rise building main distribution
Ordering and optionsOptions include choice of vacuum circuit breaker model (e.g. VS1/VTD6, VT19, VD4), auxiliary control voltages (DC110/220, AC220 V), IP4X enclosure and configurable handcart functions. Consult factory for custom layouts, short‑circuit ratings and cooling arrangements.