GeneralThe XGTD9-12 series is a three-phase indoor air-insulated, metal-enclosed fixed switchgear for power reception and distribution. Compatible with FT8-12D vacuum load switches, FT8-12RD load switch–fuse combinations and VT28 vacuum circuit breakers, it provides control, protection, monitoring and communication functions for 10 kV single-bus systems. Typical applications: airports, metros, large buildings, secondary substations and industrial sites.
Components and functions- FT8-12D vacuum load switch: compact design and reliable interlock for frequent switching.
- FT8-12RD load switch–fuse combination: adds transformer overload protection and phase-loss prevention.
- VT28 vacuum circuit breaker: control and line protection with same external dimensions for modular extension.
- Optional self-powered digital relay for protection and communications.
Standards- IEC60694 — Common specifications for high-voltage switchgear and control gear
- IEC62271-100 — AC circuit breakers
- IEC62271-200 — Metal-enclosed AC switchgear (1 kV–52 kV)
- GB/T3906, GB/T1984, GB/T3804, GB/T16926, DL/T404, DL/T402
Service conditions- Altitude: ≤ 1000 m
- Ambient temperature: +40°C max / -25°C min
- Relative humidity: daily average ≤ 95%, monthly average ≤ 90%
- No corrosive or flammable gases nearby; no frequent heavy vibration
Main technical parametersRated voltage: 12 kV
Rated frequency: 50/60 Hz
1 min power-frequency withstand voltage: 42/48 kV
Lightning impulse withstand voltage (peak): 75/85 kV
Rated main bus current: 630 A or 1250 A
Rated current of combined apparatus: 125 A / 200 A
Rated short-circuit breaking current: fuse 31.5/50 kA; circuit breaker 20, 25, 31.5 kA
Rated short-circuit withstand current / duration: 20/4, 25/4, 31.5/4 kA/s
Rated peak withstand current: 50, 63, 80 kA
Degree of protection: IP4X
Electrical parameters (load switch / combined apparatus / circuit breaker)Rated voltage: 12 / 12 / 12 kV
1 min withstand voltage: 42/48 / 42/48 / 42/48 kV
Lightning impulse withstand: 75/85 / 75/85 / 75/85 kV
Rated current: 630 A / 125/200 A / 630,1250 A
Rated short-circuit breaking current: (load switch: 20/—) / (combined: 31.5/50) / (breaker: 20,25,31.5) kA
Rated short-circuit withstand current/duration: 20/4 / — / 20/4,25/4,31.5/4 kA/s
Mechanical life (apparatus): 10000 operations
Mechanical characteristics- Contact pressure: load switch 1000 ±100 N; breaker up to 3100 ±200 N (typical intermediate values 2400 ±200 N)
- Contact opening clearance: 9 ±1 mm
- Over-travel: 5.5 ±1 mm
- Average closing speed: 0.7 ±0.2 m/s; opening speed: 1.1 ±0.2 m/s
- Contact bounce time ≤ 2 ms; asynchronous opening/closing ≤ 2 ms
Structure and operation- Enclosure: aluminium-coated zinc plate, degree of protection IP4X; front access for installation, commissioning and maintenance.
- Upper busbar compartment and lower switch/cable compartment separated by metal plate.
- Compact modular layout; live parts of each phase supported by a single insulating bushing.
- Integrated operating mechanism with five-prevention interlock to avoid misoperation.
- Identical external dimensions for breakers and load switches to simplify extension and combination; wall-mountable.
Specifications- Model: XGTD9-12
- Rated voltage: 12 kV
- Rated frequency: 50/60 Hz
- Main bus current: 630 A or 1250 A
- Short-circuit breaking capability: 20 / 25 / 31.5 kA (device dependent)
- Peak withstand currents: 50, 63, 80 kA
- Protection class: IP4X
- Mechanical life: 10,000 cycles