Frequency switchgear XGTD9-12
three-phaseACmedium-voltage

Frequency switchgear - XGTD9-12 - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage
Frequency switchgear - XGTD9-12 - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage
Frequency switchgear - XGTD9-12 - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage - image - 2
Frequency switchgear - XGTD9-12 - Ningbo Tianan (Group) CO.,Ltd. - three-phase / AC / medium-voltage - image - 3
Add to favorites
Compare this product

Characteristics

Electrical characteristics
medium-voltage, frequency, AC, three-phase
Configuration
metal-clad, air-insulated
Applications
circuit breaker, power distribution
Other characteristics
fixed
Primary current

630 A, 1,250 A

VAC

12 kV

Description

General
The XGTD9-12 series is a three-phase indoor air-insulated, metal-enclosed fixed switchgear for power reception and distribution. Compatible with FT8-12D vacuum load switches, FT8-12RD load switch–fuse combinations and VT28 vacuum circuit breakers, it provides control, protection, monitoring and communication functions for 10 kV single-bus systems. Typical applications: airports, metros, large buildings, secondary substations and industrial sites.

Components and functions
  • FT8-12D vacuum load switch: compact design and reliable interlock for frequent switching.
  • FT8-12RD load switch–fuse combination: adds transformer overload protection and phase-loss prevention.
  • VT28 vacuum circuit breaker: control and line protection with same external dimensions for modular extension.
  • Optional self-powered digital relay for protection and communications.


Standards
  • IEC60694 — Common specifications for high-voltage switchgear and control gear
  • IEC62271-100 — AC circuit breakers
  • IEC62271-200 — Metal-enclosed AC switchgear (1 kV–52 kV)
  • GB/T3906, GB/T1984, GB/T3804, GB/T16926, DL/T404, DL/T402


Service conditions
  • Altitude: ≤ 1000 m
  • Ambient temperature: +40°C max / -25°C min
  • Relative humidity: daily average ≤ 95%, monthly average ≤ 90%
  • No corrosive or flammable gases nearby; no frequent heavy vibration


Main technical parameters
Rated voltage: 12 kV
Rated frequency: 50/60 Hz
1 min power-frequency withstand voltage: 42/48 kV
Lightning impulse withstand voltage (peak): 75/85 kV
Rated main bus current: 630 A or 1250 A
Rated current of combined apparatus: 125 A / 200 A
Rated short-circuit breaking current: fuse 31.5/50 kA; circuit breaker 20, 25, 31.5 kA
Rated short-circuit withstand current / duration: 20/4, 25/4, 31.5/4 kA/s
Rated peak withstand current: 50, 63, 80 kA
Degree of protection: IP4X

Electrical parameters (load switch / combined apparatus / circuit breaker)
Rated voltage: 12 / 12 / 12 kV
1 min withstand voltage: 42/48 / 42/48 / 42/48 kV
Lightning impulse withstand: 75/85 / 75/85 / 75/85 kV
Rated current: 630 A / 125/200 A / 630,1250 A
Rated short-circuit breaking current: (load switch: 20/—) / (combined: 31.5/50) / (breaker: 20,25,31.5) kA
Rated short-circuit withstand current/duration: 20/4 / — / 20/4,25/4,31.5/4 kA/s
Mechanical life (apparatus): 10000 operations

Mechanical characteristics
  • Contact pressure: load switch 1000 ±100 N; breaker up to 3100 ±200 N (typical intermediate values 2400 ±200 N)
  • Contact opening clearance: 9 ±1 mm
  • Over-travel: 5.5 ±1 mm
  • Average closing speed: 0.7 ±0.2 m/s; opening speed: 1.1 ±0.2 m/s
  • Contact bounce time ≤ 2 ms; asynchronous opening/closing ≤ 2 ms


Structure and operation
  • Enclosure: aluminium-coated zinc plate, degree of protection IP4X; front access for installation, commissioning and maintenance.
  • Upper busbar compartment and lower switch/cable compartment separated by metal plate.
  • Compact modular layout; live parts of each phase supported by a single insulating bushing.
  • Integrated operating mechanism with five-prevention interlock to avoid misoperation.
  • Identical external dimensions for breakers and load switches to simplify extension and combination; wall-mountable.


Specifications
  • Model: XGTD9-12
  • Rated voltage: 12 kV
  • Rated frequency: 50/60 Hz
  • Main bus current: 630 A or 1250 A
  • Short-circuit breaking capability: 20 / 25 / 31.5 kA (device dependent)
  • Peak withstand currents: 50, 63, 80 kA
  • Protection class: IP4X
  • Mechanical life: 10,000 cycles

Catalogs

No catalogs are available for this product.

See all of Ningbo Tianan (Group) CO.,Ltd.‘s catalogs
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About DirectIndustry